Schneider-Electric
LV433529
Tariff code: 8536209090
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: LV433529 - circuit breaker Compact NSX250R, 200 kA at 415 VAC, Micrologic 6.2 E trip unit 250 A, 4 poles 4d
Main
Range: ComPact
Product name: ComPact NSX
Range of product: ComPact NSX100...250
Device short name: NSX250R
Product or component type: Circuit breaker
Device application: Distribution
Poles description: 4P
Protected poles description: 4t; 3t + N/2; 3t; 3t + OSN
Neutral position: Left
[In] rated current: 250 A at 40 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Suitability for isolation: Yes conforming to EN/IEC 60947-2
Utilisation category: Category A
Breaking capacity: 200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code: R 200 kA 415 V AC
Trip unit name: Micrologic 6.2 E
Trip unit technology: Electronic
Trip unit protection functions: LSIG
control type: Toggle
Mounting mode: Fixed
Complementary
[Ui] rated insulation voltage: 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 8 kV
[Ics] rated service breaking capacity: 200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability: 20000 cycles
Electrical durability: 5000 cycles at 690 V In; 10000 cycles at 690 V In/2; 10000 cycles at 440 V In; 20000 cycles at 440 V In/2
Mounting support: Backplate
upside connection: Front
Downside connection: Front
Connection pitch: 35 mm
Protection type: L : for overload protection (long time); S : for short time short-circuit protection; I : for instantaneous short-circuit protection; G : for ground fault protection
Trip unit rating: 250 A at 40 °C
Long time pick-up adjustment type Ir: Adjustable 9 settings
long time pick-up adjustment range: 100...250 A
long time delay adjustment type: Adjustable
[tr] long-time delay adjustment range: 15…400 s at 1.5 x Ir; 0.35…11 s at 7.2 x Ir; 0.5…16 s at 6 x Ir
Thermal memory: 20 minutes before and after tripping
Short-time pick-up adjustment type Isd: Adjustable
[Isd] short-time pick-up adjustment range: 1.5...12 x In
Short-time delay adjustment type: Adjustable 5 settings
[tsd] short-time delay adjustment range: 0…0.4 s
Instantaneous pick-up adjustment type Ii: Adjustable
Instantaneous pick-up adjustment range: 1.5...12 x In
Ground-fault pick-up adjustment type: Adjustable 9 settings
[Ig] ground-fault pick-up adjustment range: 0.2...1 x In; Ig enable on/off
Ground-fault time delay adjustment type -tg: Adjustable 5 settings
[tg] Ground-fault time delay adjustment range: 0…0.4 s I²t=off; 0.1…0.4 s I²t=on
Earth-leakage protection: Without
Neutral protection setting: 0.5 x Ir (3t + N/2); 1 x Ir (4t); 1.6 x Ir (3t + OSN); No protection (3t)
Zone selective interlocking ZSI: With
Number of slots: 5 slot(s)
Local signalling: Flashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload
Display type: LCD display
type of measurement: Energy meter
Communication of data: Maximeters/minimeters; Power quality; Demand current and power; Protection and alarm settings; Energy metering; Time-stamped histories and event tables; Instantaneous and demand values; Maintenance indicators
Width: 140 mm
Height: 161 mm
Depth: 86 mm
Net weight: 2.8 kg
Compatibility code: NSX250
Environment
Standards: EN/IEC 60947
Product certifications: Marine; CCC; EAC
Overvoltage category: Class II
Electrical shock protection class: Class II
Pollution degree: 3 conforming to IEC 60664-1
IP degree of protection: IP40 conforming to IEC 60529
IK degree of protection: IK07 conforming to IEC 62262
Ambient air temperature for operation: -25…70 °C
Ambient air temperature for storage: -40…85 °C
Relative humidity: 0…95 %
Operating altitude: 0...2000 m without derating; 2000 m...5000 m with derating
Packing Units
Unit Type of Package 1: Db
Number of Units in Package 1: 1
Package 1 Height: 13.5 cm
Package 1 Width: 14.1 cm
Package 1 Length: 19.2 cm
Package 1 Weight: 2.711 kg
Offer Sustainability
Sustainable offer status: Green Premium product
EU RoHS Directive: Compliant
Mercury free: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP120606EN
Circularity Profile: ENVEOLI120604EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.