Skip to main content

Schneider-Electric
LV430331

circuit breaker Compact NSX160B, 25 kA at 415 VAC, TMD trip unit 125 A, 4 poles 4d
Barcode: 3606480011191
Tariff code: 8536209090

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: LV430331 - circuit breaker Compact NSX160B, 25 kA at 415 VAC, TMD trip unit 125 A, 4 poles 4d

Main

Range: ComPact

Product name: ComPact NSX

Range of product: ComPact NSX100...250

Device short name: NSX160B

Product or component type: Circuit breaker

Device application: Distribution

Poles description: 4P

Protected poles description: 4t

Neutral position: Left

[In] rated current: 125 A at 40 °C

[Ue] rated operational voltage: 690 V AC 50/60 Hz

Network type: AC

Network frequency: 50/60 Hz

Suitability for isolation: Yes conforming to EN/IEC 60947-2

Utilisation category: Category A

Breaking capacity: 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2

Breaking capacity code: B 25 kA 415 V AC

Trip unit name: TM-D

Trip unit technology: Thermal-magnetic

Trip unit protection functions: LI

control type: Toggle

Mounting mode: Fixed

Complementary

[Ui] rated insulation voltage: 800 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage: 8 kV

[Ics] rated service breaking capacity: 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical durability: 40000 cycles

Electrical durability: 7500 cycles at 690 V In; 15000 cycles at 690 V In/2; 20000 cycles at 440 V In; 40000 cycles at 440 V In/2

Mounting support: Backplate

upside connection: Front

Downside connection: Front

Connection pitch: 35 mm

Protection type: L : for overload protection (thermal); I : for short-circuit protection (magnetic)

Trip unit rating: 125 A at 40 °C

Long time pick-up adjustment type Ir: Adjustable

long time pick-up adjustment range: 0.7...1 x In

long time delay adjustment type: Fixed

[tr] long-time delay adjustment range: 120…400 s at 1.5 x In; 15 s at 6 x Ir

Short-time pick-up adjustment type Isd: Fixed

[Isd] short-time pick-up adjustment range: 1250 A

Short-time delay adjustment type: Fixed

Earth-leakage protection: Without

Neutral protection setting: 1 x Ir (4t)

Number of slots: 5 slot(s)

Width: 140 mm

Height: 161 mm

Depth: 86 mm

Net weight: 2.6 kg

Compatibility code: NSX160

Environment

Standards: EN/IEC 60947

Product certifications: CCC; EAC; Marine

Overvoltage category: Class II

Electrical shock protection class: Class II

Pollution degree: 3 conforming to IEC 60664-1

IP degree of protection: IP40 conforming to IEC 60529

IK degree of protection: IK07 conforming to IEC 62262

Ambient air temperature for operation: -25…70 °C

Ambient air temperature for storage: -50…85 °C

Relative humidity: 0…95 %

Operating altitude: 0...2000 m without derating; 2000 m...5000 m with derating

Packing Units

Unit Type of Package 1: Db

Number of Units in Package 1: 1

Package 1 Height: 14.400 cm

Package 1 Width: 15.000 cm

Package 1 Length: 19.200 cm

Package 1 Weight: 2.428 kg

Unit Type of Package 2: Doboz

Number of Units in Package 2: 4

Package 2 Height: 30.000 cm

Package 2 Width: 30.000 cm

Package 2 Length: 40.000 cm

Package 2 Weight: 10.153 kg

Offer Sustainability

Sustainable offer status: Green Premium product

EU RoHS Directive: Compliant

Mercury free: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP120606EN

Circularity Profile: ENVEOLI120604EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

© 2018 Alplan Kft.