Link to the manufacturers site: LV429936 - circuit breaker Vigicompact NSX 100F, 36 kA at 415 VAC, TM-D trip unit 25 A, add-on Vigi MH module, 3P 3d
Main
range: ComPact
product name: ComPact NSX
range of product: ComPact NSX100...250
device short name: VigiCompact NSX100F
product or component type: Circuit breaker with Vigi add-on
device application: Distribution
poles description: 3P
protected poles description: 3t
[In] rated current: 25 A at 40 °C
[Ue] rated operational voltage: 440 V AC 50/60 Hz
network type: AC
network frequency: 50/60 Hz
suitability for isolation: Yes conforming to EN/IEC 60947-2
utilisation category: Category A
breaking capacity: 10 kA at 600 V AC 50/60 Hz conforming to UL 508; 25 kA at 480 V AC 50/60 Hz conforming to UL 508; 85 kA at 240 V AC 50/60 Hz conforming to UL 508; 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code: F 36 kA 415 V AC
trip unit name: TM-D
trip unit technology: Thermal-magnetic
trip unit protection functions: LI
control type: Toggle
mounting mode: Fixed
Complementary
[Ui] rated insulation voltage: 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 8 kV
[Ics] rated service breaking capacity: 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 12.5 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
mechanical durability: 50000 cycles
electrical durability: 10000 cycles at 690 V In; 20000 cycles at 690 V In/2; 30000 cycles at 440 V In; 50000 cycles at 440 V In/2
mounting support: Backplate
upside connection: Front
downside connection: Front
connection pitch: 35 mm
protection type: L : for overload protection (thermal); I : for short-circuit protection (magnetic)
trip unit rating: 25 A at 40 °C
long time pick-up adjustment type Ir: Adjustable
long time pick-up adjustment range: 0.7...1 x In
long time delay adjustment type: Fixed
[tr] long-time delay adjustment range: 120…400 s at 1.5 x In; 15 s at 6 x Ir
short-time pick-up adjustment type Isd: Fixed
[Isd] short-time pick-up adjustment range: 300 A
short-time delay adjustment type: Fixed
earth-leakage protection: With
earth-leakage add-on module name: MH
earth-leakage protection class: Class A
residual earth-leakage sensitity adjustment type: Adjustable 5 settings
[IΔn] residual earth-leakage sensitive adjustment: 0.03…10 A
residual earth-leakage time delay adjustment type: Adjustable 4 settings
number of slots: 6 slot(s)
width: 105 mm
height: 236 mm
depth: 86 mm
net weight: 2.05 kg
compatibility code: NSX100
Environment
standards: EN/IEC 60947
product certifications: CCC; EAC; Marine
overvoltage category: Class II
electrical shock protection class: Class II
pollution degree: 3 conforming to IEC 60664-1
IP degree of protection: IP40 conforming to IEC 60529
IK degree of protection: IK07 conforming to IEC 62262
ambient air temperature for operation: -25…70 °C
ambient air temperature for storage: -50…85 °C
relative humidity: 0…95 %
operating altitude: 0...2000 m without derating; 2000 m...5000 m with derating
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure: ENVPEP120606EN
Circularity Profile: ENVEOLI120604EN
PVC free: Yes