Skip to main content

Schneider-Electric
LV429140

trip unit Micrologic 6.2 E for Compact NSX 100/160/250 circuit breakers, electronic, rating 100A, 4 poles 4d
Barcode: 3606480017087
Tariff code: 8536303099

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: LV429140 - trip unit Micrologic 6.2 E for Compact NSX 100/160/250 circuit breakers, electronic, rating 100A, 4 poles 4d

Main

Range: ComPact

Range of product: ComPact NSX100...250

Product name: Micrologic

Product or component type: Trip unit

Trip unit name: Micrologic 6.2 E

Trip unit technology: Electronic

Range compatibility: ComPact NSX100; ComPact NSX160; ComPact NSX250

Device application: Distribution

Poles description: 4P

Protected poles description: 3t + OSN; 4t; 3t + N/2; 3t

Neutral position: Left

Trip unit protection functions: LSIG

Protection type: L : for overload protection (long time); S : for short time short-circuit protection; I : for instantaneous short-circuit protection; G : for ground fault protection

[In] rated current: 100 A at 40 °C

[Ue] rated operational voltage: 690 V AC 50/60 Hz

Network type: AC

Network frequency: 50/60 Hz

Complementary

Long time pick-up adjustment type Ir: Adjustable 9 settings

long time pick-up adjustment range: 40...100 A

long time delay adjustment type: Adjustable

[tr] long-time delay adjustment range: 15…400 s at 1.5 x Ir; 0.35…11 s at 7.2 x Ir; 0.5…16 s at 6 x Ir

Thermal memory: 20 minutes before and after tripping

Short-time pick-up adjustment type Isd: Adjustable 9 settings

[Isd] short-time pick-up adjustment range: 1.5...10 x Ir

Short-time delay adjustment type: Adjustable

[tsd] short-time delay adjustment range: 0…0.4 s I²t=off; 0.1…0.4 s I²t=on

Instantaneous pick-up adjustment type Ii: Adjustable

Instantaneous pick-up adjustment range: 1.5...12 x In Compact NSX250; 1.5...15 x In Compact NSX100; 1.5...15 x In Compact NSX160

Ground-fault pick-up adjustment type: Adjustable

[Ig] ground-fault pick-up adjustment range: 0.2...1 x In for In = 40 A; 0.4...1 x In for In > 40 A; Ig enable on/off

Ground-fault time delay adjustment type -tg: Adjustable

[tg] Ground-fault time delay adjustment range: 0…0.4 s I²t=off; 0.1…0.4 s I²t=on

Earth-leakage protection: Without

Neutral protection setting: 0.5 x Ir (3t + N/2); 1 x Ir (4t); 1.6 x Ir (3t + OSN); No protection (3t)

Zone selective interlocking ZSI: With

Local signalling: Flashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload

Display type: LCD display

type of measurement: Energy meter

Communication of data: Power quality; Demand current and power; Instantaneous and demand values; Maximeters/minimeters; Protection and alarm settings; Time-stamped histories and event tables; Energy metering; Maintenance indicators

Electrical data recording: Maintenance indicators

Environment

Standards: EN/IEC 60947-2; UL 508

Product certifications: EAC; Marine; CCC

Ambient air temperature for operation: -25…70 °C

Ambient air temperature for storage: -40…85 °C

Packing Units

Unit Type of Package 1: Db

Number of Units in Package 1: 1

Package 1 Height: 9.8 cm

Package 1 Width: 11 cm

Package 1 Length: 15 cm

Package 1 Weight: 680 g

Unit Type of Package 2: Doboz

Number of Units in Package 2: 11

Package 2 Height: 30 cm

Package 2 Width: 30 cm

Package 2 Length: 40 cm

Package 2 Weight: 7.889 kg

Offer Sustainability

Sustainable offer status: Green Premium product

EU RoHS Directive: Compliant

Mercury free: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP120606EN

Circularity Profile: ENVEOLI120604EN