Skip to main content

Schneider-Electric
LV429111

trip unit Micrologic 6.2 A for Compact NSX 100/160/250 circuit breakers, electronic, rating 40A, 3 poles 3d
Barcode: 3606480016615
Tariff code: 8536303099

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: LV429111 - trip unit Micrologic 6.2 A for Compact NSX 100/160/250 circuit breakers, electronic, rating 40A, 3 poles 3d

Main

range: ComPact

range of product: ComPact NSX100...250

product name: Micrologic

product or component type: Trip unit

trip unit name: Micrologic 6.2 A

trip unit technology: Electronic

range compatibility: ComPact NSX100; ComPact NSX160; ComPact NSX250

device application: Distribution

poles description: 3P

protected poles description: 3t

trip unit protection functions: LSIG

protection type: L : for overload protection (long time); S : for short time short-circuit protection; I : for instantaneous short-circuit protection; G : for ground fault protection

[In] rated current: 40 A at 40 °C

[Ue] rated operational voltage: 690 V AC 50/60 Hz

network type: AC

network frequency: 50/60 Hz

Complementary

long time pick-up adjustment type Ir: Adjustable 9 settings

long time pick-up adjustment range: 18...40 A

long time delay adjustment type: Adjustable

[tr] long-time delay adjustment range: 15…400 s at 1.5 x Ir; 0.35…11 s at 7.2 x Ir; 0.5…16 s at 6 x Ir

thermal memory: 20 minutes before and after tripping

short-time pick-up adjustment type Isd: Adjustable 9 settings

[Isd] short-time pick-up adjustment range: 1.5...10 x Ir

short-time delay adjustment type: Adjustable

[tsd] short-time delay adjustment range: 0…0.4 s I²t=off; 0.1…0.4 s I²t=on

instantaneous pick-up adjustment type Ii: Adjustable

instantaneous pick-up adjustment range: 1.5...12 x In Compact NSX250; 1.5...15 x In Compact NSX100; 1.5...15 x In Compact NSX160

ground-fault pick-up adjustment type: Adjustable

[Ig] ground-fault pick-up adjustment range: 0.2...1 x In for In = 40 A; 0.4...1 x In for In > 40 A; Ig enable on/off

ground-fault time delay adjustment type -tg: Adjustable

[tg] ground-fault time delay adjustment range: 0…0.4 s I²t=off; 0.1…0.4 s I²t=on

earth-leakage protection: Without

zone selective interlocking ZSI: With

local signalling: Flashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload

display type: LCD display

type of measurement: Ammeter

communication of data: Power quality; Maximeters/minimeters; Protection and alarm settings; Time-stamped histories and event tables; Demand current and power; Energy metering; Maintenance indicators; Instantaneous and demand values

electrical data recording: Maintenance indicators

Environment

standards: UL 508; EN/IEC 60947-2

product certifications: Marine; CCC; EAC

ambient air temperature for operation: -25…70 °C

ambient air temperature for storage: -40…85 °C

Offer Sustainability

Sustainable offer status: Green Premium product

EU RoHS Directive: Compliant

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure: ENVPEP120606EN

Circularity Profile: ENVEOLI120604EN

© 2018 Alplan Kft.