Main

range: EasyPact

product name: EasyPact TVS

product or component type: Contactor

device short name: LC1E

contactor application: Resistive load; Motor control

utilisation category: AC-3; AC-1

poles description: 3P

pole contact composition: 3 NO

[Ue] rated operational voltage: Power circuit: <= 690 V AC 50/60 Hz

[Ie] rated operational current: 500 A (at <55 °C) at <= 440 V AC AC-3 for power circuit; 700 A (at <55 °C) at <= 440 V AC AC-1 for power circuit

motor power kW: 147 kW at 220...230 V AC 50/60 Hz; 250 kW at 380...400 V; 280 kW at 415 V; 295 kW at 440 V; 335 kW at 500 V; 355 kW at 660...690 V

control circuit type: AC at 50/60 Hz

[Uc] control circuit voltage: 48 V AC 50/60 Hz

height: 400 mm

width: 233 mm

depth: 232 mm

net weight: 11.35 kg

Complementary

[Uimp] rated impulse withstand voltage: 8 kV coil not connected to the power circuit conforming to IEC 60947

[Ui] rated insulation voltage: 690 V conforming to IEC 60947-4-1

overvoltage category: III

[Ith] conventional free air thermal current: 700 A (at 40 °C) for power circuit

Irms rated making capacity: 5000 A at 440 V AC for power circuit conforming to IEC 60947-4-1

rated breaking capacity: 4000 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current: 4200 A 40 °C - 10 s for power circuit

associated fuse rating: 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1; 800 A gG at <= 690 V coordination type 1 for power circuit

average impedance: 0.18 mOhm - Ith 700 A 50 Hz for power circuit

power dissipation per pole: 45 W AC-3; 88 W AC-1

control circuit voltage limits: Operational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C); Drop-out: 0.35...0.5 Uc at 50/60 Hz (at <55 °C)

operating time: 100...170 ms on opening; 40...75 ms on closing

mechanical durability: 4000000 cycles

maximum operating rate: 2400 cyc/h 55 °C

inrush power in VA: 1100 VA 50 Hz cos phi 0.9 (at 20 °C); 1100 VA 60 Hz cos phi 0.9 (at 20 °C)

hold-in power consumption in VA: 18 VA 50 Hz cos phi 0.9 (at 20 °C); 18 VA 60 Hz cos phi 0.9 (at 20 °C)

heat dissipation: 18 W for control circuit; 18 W

minimum switching current: 5 mA for control circuit

minimum switching voltage: 17 V for control circuit

non-overlap time: 1.5 ms on energisation guaranteed between NC and NO contact; 1.5 ms on de-energisation guaranteed between NC and NO contact

insulation resistance: > 10 MOhm for control circuit

electrical durability: 250000 cycles AC-1; 600000 cycles AC-3

mounting support: Plate

connections - terminals: Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end; Power circuit: cable with lug 2 - external diameter: 240 mm; Power circuit: bars 2 - busbar cross section: 40 x 5 mm

tightening torque: Control circuit: 1.2 N.m; Power circuit: 35 N.m

Environment

standards: IEC 60947-5-1; IEC 60947-4-1; IEC 60947-1

product certifications: EAC; CE

IP degree of protection: IP00 conforming to IEC 60529

protective treatment: (pollution degree 3)

pollution degree: 3

ambient air temperature for operation: -5…55 °C

ambient air temperature for storage: -60…80 °C

permissible ambient air temperature around the device: -20…70 °C at Uc

operating altitude: 3000 m without derating

fire resistance: 850 °C conforming to IEC 60695-2-1

mechanical robustness: Shocks contactor closed: 15 Gn for 11 ms; Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 4 Gn, 5...300 Hz; Shocks contactor open: 9 Gn for 11 ms