LC1D40008M7

TeSys D contactor - 4P(2 NO + 2 NC) - AC-1 <= 440 V 60 A 220 V AC 50/60 Hz coil
Net discounted price 247.34 EUR
Available when ordered (delivery time: 6 working day(s))
Barcode: 3389110231595
Tariff code: 8536490099

Link to the manufacturers site: LC1D40008M7 - TeSys D contactor - 4P(2 NO + 2 NC) - AC-1 <= 440 V 60 A 220 V AC 50/60 Hz coil

Main

Range: TeSys

Range of produc: TeSys Deca

Product or component type: Contactor

Device short name: LC1D

contactor application: Resistive load

utilisation category: AC-1

Poles description: 4P

[Ue] rated operational voltage: Power circuit: <= 690 V AC 25...400 Hz; Power circuit: <= 300 V DC

[Ie] rated operational current: 60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

[Uc] control circuit voltage: 220 V AC 50/60 Hz

Complementary

Compatibility code: LC1D

Pole contact composition: 2 NO + 2 NC

Contact compatibility: M1

Protective cover: Without

[Ith] conventional free air thermal current: 60 A (at 60 °C) for power circuit

Irms rated making capacity: 800 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity: 800 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current: 320 A 40 °C - 10 s for power circuit; 720 A 40 °C - 1 s for power circuit; 72 A 40 °C - 10 min for power circuit; 165 A 40 °C - 1 min for power circuit

Associated fuse rating: 80 A gG at <= 690 V coordination type 1 for power circuit; 80 A gG at <= 690 V coordination type 2 for power circuit

Average impedance: 1.5 mOhm - Ith 60 A 50 Hz for power circuit

Power dissipation per pole: 5.4 W AC-1

[Ui] rated insulation voltage: Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 690 V conforming to IEC 60947-4-1

Overvoltage category: III

Pollution degree: 3

[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947

Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability: 6 Mcycles

Electrical durability: 1.4 Mcycles 60 A AC-1 at Ue <= 440 V

Control circuit type: AC at 50/60 Hz

Coil technology: Without built-in suppressor module

Control circuit voltage limits: 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz

Inrush power in VA: 140 VA 60 Hz cos phi 0.75 (at 20 °C); 160 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in VA: 13 VA 60 Hz cos phi 0.3 (at 20 °C); 15 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation: 4…5 W at 50/60 Hz

Operating time: 4...19 ms opening; 12...26 ms closing

Maximum operating rate: 3600 cyc/h 60 °C

Connections - terminals: Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end; Power circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: solid without cable end; Power circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: solid without cable end

Tightening torque: Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 8 N.m - on screw clamp terminals - cable 25…35 mm² hexagonal screw head 4 mm; Power circuit: 5 N.m - on screw clamp terminals - cable 1…25 mm² hexagonal screw head 4 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

mounting support: Plate; Rail

Environment

Standards: CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 508

product certifications: RINA; GL; UL; GOST; BV; LROS (Lloyds register of shipping); DNV; CCC; CSA

IP degree of protection: IP20 front face conforming to IEC 60529

Protective treatment: TH conforming to IEC 60068-2-30

Climatic withstand: conforming to IACS E10 exposure to damp heat

Permissible ambient air temperature around the device: -40…60 °C; 60…70 °C with derating

Operating altitude: 0...3000 m

Fire resistance: 850 °C conforming to IEC 60695-2-1

Flame retardance: V1 conforming to UL 94

Mechanical robustness: Shocks contactor open (8 Gn for 11 ms) ; Shocks contactor closed (10 Gn for 11 ms) ; Vibrations contactor opened (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz)

height: 127 mm

Width: 85 mm

Depth: 125 mm

Net weight: 1.44 kg

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 11.2 cm

Package 1 Width: 13.5 cm

Package 1 Length: 15.2 cm

Package 1 Weight: 1.47 kg

Unit Type of Package 2: S02

Number of Units in Package 2: 5

Package 2 Height: 15 cm

Package 2 Width: 30 cm

Package 2 Length: 40 cm

Package 2 Weight: 7.605 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

China RoHS Regulation:  Pro-active China RoHS declaration (out of China RoHS legal scope)

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP110205EN

Circularity Profile: N/A

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins