Schneider-Electric
BMXDRA1605H
Tariff code: 8538909999
Link to the manufacturers site: BMXDRA1605H - discrete output module X80 - 16O relay - 24VDC - 24..240VAC - severe environment
Main
Range of produc: Modicon X80
Product or component type: Discrete output module
Product specific application: For severe environments
Discrete output number: 16 conforming to IEC 61131-2
Discrete output type: Relay
Discrete output voltage: 24...48 V 19...60 V DC; 24...240 V 19…264 V AC
Complementary
[Ith] conventional free air thermal current: 2 A
Insulation resistance: > 10 MOhm 500 V DC
Power dissipation in W: 3 W
Response time on output: < 8 ms activation; < 10 ms deactivation
Typical current consumption: 100 mA at 3.3 V DC; 95 mA at 24 V DC
MTBF reliability: 2100000 H
Output overload protection: Use 1 fast blow fuse per channel or group of channel
Output overvoltage protection: Use discharge diode on each output DC; Use RC circuit on each output AC; Use ZNO surge limiter on each output AC
Output short-circuit protection: Use 1 fast blow fuse per channel or group of channel
Minimum switching current: 1 mA 5 V DC
Electrical durability: AC-15: 100000 cycles at 240 VA 200 V (load factor 0.7); AC-15: 100000 cycles at 120 VA 200 V (load factor 0.35); AC-12: 100000 cycles at 200 VA 100 V; AC-12: 100000 cycles at 80 VA 48 V; AC-12: 100000 cycles at 50 VA 24 V; AC-15: 100000 cycles at 120 VA 100 V; AC-15: 100000 cycles at 120 VA 24 V; AC-15: 100000 cycles at 120 VA 48 V; DC-12: 100000 cycles at 24 W 24 V; DC-13: 100000 cycles at 10 W 24 V; DC-13: 100000 cycles at 10 W 48 V; AC-15: 300000 cycles at 72 VA 200 V (load factor 0.7); AC-15: 300000 cycles at 36 VA 200 V (load factor 0.35); AC-12: 300000 cycles at 200 VA 200 V; AC-12: 300000 cycles at 80 VA 100 V; AC-12: 300000 cycles at 50 VA 48 V; AC-15: 300000 cycles at 36 VA 100 V; AC-15: 300000 cycles at 72 VA 100 V; AC-15: 300000 cycles at 36 VA 48 V; AC-15: 300000 cycles at 72 VA 48 V; AC-15: 300000 cycles at 36 VA 24 V; AC-15: 300000 cycles at 72 VA 24 V; DC-13: 300000 cycles at 3 W 24 V; DC-13: 300000 cycles at 3 W 48 V; DC-13: 7000 cycles at 24 W 24 V; DC-13: 7000 cycles at 24 W 48 V; DC-12: 50000 cycles at 24 W 48 V
Status LED: 1 LED (green) RUN; 1 LED per channel (green) channel diagnostic; 1 LED (red) ERR; 1 LED (red) I/O
Net weight: 0.15 kg
Environment
IP degree of protection: IP20
Directives: 2014/35/EU - low voltage directive; 2014/30/EU - electromagnetic compatibility
Environmental characteristic: Gas resistant class Gx; Gas resistant class 3C4; Dust resistant class 3S4; Sand resistant class 3S4; Salt resistant level 2; Mold growth resistant class 3B2; Fungal spore resistant class 3B2
Dielectric strength: 2000 V AC at 50/60 Hz 1 min
Vibration resistance: 3 gn
Shock resistance: 30 gn
Ambient air temperature for storage: -40…85 °C
ambient air temperature for operation: -25…70 °C
Relative humidity: 5…95 % at 55 °C without condensation
Protective treatment: Conformal coating
Operating altitude: 0...2000 m; 2000...5000 m with derating factor
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 5.5 cm
Package 1 Width: 11.0 cm
Package 1 Length: 11.6 cm
Package 1 Weight: 190.0 g
Unit Type of Package 2: S02
Number of Units in Package 2: 15
Package 2 Height: 15.0 cm
Package 2 Width: 30.0 cm
Package 2 Length: 40.0 cm
Package 2 Weight: 3.15 kg
Offer Sustainability
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
China RoHS Regulation: X
RoHS exemption information: Yes
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins