Schneider-Electric
BMXCPS4002
Tariff code: 8504409590
Link to the manufacturers site: BMXCPS4002 - X80 tápegység, redundáns, 100…230 VAC, 40W
Main
Range of produc: Modicon X80
Product or component type: Power supply module
Product compatibility: All backplane
Function available: Temperature sensing; Redundancy test; Uptime duration; Redundancy information; Remaining lifetime
Primary voltage: 100...240 V
Supply circuit type: AC
Secondary power: 18 W 3.3 V DC at 0…60 °C I/O module logic power supply; 40 W 24 V DC at 0…60 °C I/O module power supply and processor if 3.3 V not loaded
Complementary
Primary voltage limit: 85...264 V
Network frequency: 50/60 Hz
network frequency limits: 47…63 Hz
Apparent power: 0.13 kVA
Input current: 0.55 A 240 V; 1.01 A 115 V
Inrush current: 30 A 120 V; 60 A 240 V
I²t on activation: 1 A².s 115 V; 4 A².s 230 V
It on activation: 0.1 A.s 115 V; 0.15 A.s 230 V
MTBF reliability: 792000 H
Protection type: Internal fuse not accessible for primary circuit; Overload protection for secondary circuit; Overvoltage protection for secondary circuit; Short-circuit protection for secondary circuit
Current at secondary voltage: 5.5 A 3.3 V DC I/O module logic power supply; 1.67 A 24 V DC I/O module power supply and processor
maximum power dissipation in W: 8.5 W
Status LED: 1 LED (green) presence of voltages (OK); 1 LED (green) redundancy OK; 1 LED (green) power supply status
control type: RESET push-button cold restart
Electrical connection: 1 connector 2 pin(s)alarm relay; 1 connector 5 pin(s)line supply, protective earth
Insulation resistance: >= 100 MOhm primary/ground; >= 100 MOhm primary/secondary
Net weight: 0.51 kg
Environment
Immunity to microbreaks: 1 ms
Dielectric strength: 1500 V primary/secondary I/O module logic power supply; 1500 V primary/secondary I/O module power supply and processor; 2300 V primary/secondary sensor power supply; 1500 V primary/ground; 500 V 24 V sensor output/ground
Vibration resistance: 3 gn
Shock resistance: 30 gn
IP degree of protection: IP20
Directives: 2014/35/EU - low voltage directive; 2014/30/EU - electromagnetic compatibility
Environmental characteristic: 3C3 conforming to EN/IEC 60721-3-3; 3C4 conforming to EN/IEC 60721-3-3
Ambient air temperature for storage: -40…85 °C
ambient air temperature for operation: 0…60 °C
Relative humidity: 5…95 % at 55 °C without condensation
Protective treatment: TC; Conformal coating Humiseal 1A33
Operating altitude: 0...2000 m; 2000...5000 m with derating factor
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 8.83 cm
Package 1 Width: 17.68 cm
Package 1 Length: 25.019 cm
Package 1 Weight: 611.0 g
Unit Type of Package 2: S03
Number of Units in Package 2: 6
Package 2 Height: 30 cm
Package 2 Width: 30 cm
Package 2 Length: 40 cm
Package 2 Weight: 4.54 kg
Unit Type of Package 3: P06
Number of Units in Package 3: 48
Package 3 Height: 75 cm
Package 3 Width: 60 cm
Package 3 Length: 80 cm
Package 3 Weight: 50 kg
Offer Sustainability
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
China RoHS Regulation: X
RoHS exemption information: Yes
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins