Schneider-Electric
ATV312HU55N4
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: ATV312HU55N4 - variable speed drive ATV312 - 5.5kW - 15kVA - 232W - 380..500 V- 3-phase supply
Main
range of product: Altivar 312
product or component type: Variable speed drive
product destination: Asynchronous motors
product specific application: Simple machine
assembly style: With heat sink
component name: ATV312
motor power kW: 5.5 kW
motor power hp: 7.5 hp
[Us] rated supply voltage: 380...500 V - 15...10 %
supply frequency: 50...60 Hz - 5...5 %
network number of phases: 3 phases
line current: 21.9 A at 380 V, Isc = 22 kA; 16.5 A at 500 V
EMC filter: Integrated
apparent power: 15 kVA
maximum transient current: 21.5 A for 60 s
power dissipation in W: 232 W at nominal load
speed range: 1…50
asynchronous motor control profile: Factory set : constant torque; Sensorless flux vector control with PWM type motor control signal
electrical connection: Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1...LI6 terminal 2.5 mm² AWG 14; L1, L2, L3, U, V, W, PA, PB, PA/+, PC/- terminal 16 mm² AWG 6
supply: Internal supply for logic inputs: 19...30 V 100 mA, protection type: overload and short-circuit protection; Internal supply for reference potentiometer (2.2 to 10 kOhm): 10...10.8 V 10 mA, protection type: overload and short-circuit protection
communication port protocol: Modbus; CANopen
IP degree of protection: IP20 on upper part without cover plate; IP21 on connection terminals; IP31 on upper part; IP41 on upper part
option card: Communication card for CANopen daisy chain; Communication card for DeviceNet; Communication card for Fipio; Communication card for Modbus TCP; Communication card for Profibus DP
Complementary
supply voltage limits: 323…550 V
prospective line Isc: 22 kA
continuous output current: 14.3 A at 4 kHz
output frequency: 0…500 Hz
nominal switching frequency: 4 kHz
switching frequency: 2...16 kHz adjustable
transient overtorque: 170…200 % of nominal motor torque
braking torque: 150 % during 60 s with braking resistor; 100 % with braking resistor continuously; 150 % without braking resistor
regulation loop: Frequency PI regulator
motor slip compensation: Automatic whatever the load; Adjustable; Suppressable
output voltage: <= power supply voltage
tightening torque: Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1...LI6: 0.6 N.m; L1, L2, L3, U, V, W, PA, PB, PA/+, PC/-: 2.5 N.m
insulation: Electrical between power and control
analogue input number: 3
analogue input type: AI1 configurable voltage 0...10 V, input voltage 30 V max, impedance: 30000 Ohm; AI2 configurable voltage +/- 10 V, input voltage 30 V max, impedance: 30000 Ohm; AI3 configurable current 0...20 mA, impedance: 250 Ohm
sampling duration: AI1, AI2, AI3: 8 ms analog; LI1...LI6: 4 ms discrete
response time: AOV, AOC 8 ms for analog; R1A, R1B, R1C, R2A, R2B 8 ms for discrete
linearity error: +/- 0.2 % for output
analogue output number: 1
analogue output type: AOC configurable current: 0...20 mA, impedance: 800 Ohm, resolution: 8 bits; AOV configurable voltage: 0...10 V, impedance: 470 Ohm, resolution: 8 bits
discrete input logic: Logic input not wired (LI1...LI4), < 13 V (state 1); Negative logic (source) (LI1...LI6), > 19 V (state 0); Positive logic (source) (LI1...LI6), < 5 V (state 0), > 11 V (state 1)
discrete output number: 2
discrete output type: Configurable relay logic: (R1A, R1B, R1C) 1 NO + 1 NC - 100000 cycles; Configurable relay logic: (R2A, R2B) NC - 100000 cycles
minimum switching current: R1-R2 10 mA at 5 V DC
maximum switching current: R1-R2: 2 A at 250 V AC inductive load, cos phi = 0.4 and L/R = 7 ms; R1-R2: 2 A at 30 V DC inductive load, cos phi = 0.4 and L/R = 7 ms; R1-R2: 5 A at 250 V AC resistive load, cos phi = 1 and L/R = 0 ms; R1-R2: 5 A at 30 V DC resistive load, cos phi = 1 and L/R = 0 ms
discrete input number: 6
discrete input type: (LI1...LI6) programmable at 24 V, 0…100 mA for PLC, impedance: 3500 Ohm
acceleration and deceleration ramps: Linear adjustable separately from 0.1 to 999.9 s; S, U or customized
braking to standstill: By DC injection
protection type: Input phase breaks: drive; Line supply overvoltage and undervoltage safety circuits: drive; Line supply phase loss safety function, for three phases supply: drive; Motor phase breaks: drive; Overcurrent between output phases and earth (on power up only): drive; Overheating protection: drive; Short-circuit between motor phases: drive; Thermal protection: motor
insulation resistance: >= 500 mOhm 500 V DC for 1 minute
local signalling: 1 LED (red) for drive voltage; Four 7-segment display units for CANopen bus status
time constant: 5 ms for reference change
frequency resolution: Analog input: 0.1...100 Hz; Display unit: 0.1 Hz
connector type: 1 RJ45 for Modbus/CANopen
physical interface: RS485 multidrop serial link
transmission frame: RTU
transmission rate: 10, 20, 50, 125, 250, 500 kbps or 1 Mbps for CANopen; 4800, 9600 or 19200 bps for Modbus
number of addresses: 1…127 for CANopen; 1…247 for Modbus
number of drive: 127 for CANopen; 31 for Modbus
marking: CE
operating position: Vertical +/- 10 degree
outer dimension: 442 x 239 x 192 mm; 300 x 210 x 170 mm; 232 x 180 x 170 mm; 402 x 239 x 192 mm
height: 232 mm
width: 180 mm
depth: 172 mm
net weight: 6.5 kg
network frequency: 47.5...63 Hz
Environment
dielectric strength: 2410 V DC between earth and power terminals; 3400 V AC between control and power terminals
electromagnetic compatibility: 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
standards: IEC 61800-5-1; IEC 61800-3
product certifications: GOST; DNV; NOM; UL; CSA; C-Tick
pollution degree: 2
protective treatment: TC
vibration resistance: 1 gn (f= 13…150 Hz) conforming to EN/IEC 60068-2-6; 1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6
shock resistance: 15 gn for 11 ms conforming to EN/IEC 60068-2-27
relative humidity: 5…95 % without condensation conforming to IEC 60068-2-3; 5…95 % without dripping water conforming to IEC 60068-2-3
ambient air temperature for storage: -25…70 °C
ambient air temperature for operation: -10…50 °C without derating (with protective cover on top of the drive); -10…60 °C with derating factor (without protective cover on top of the drive)
operating altitude: <= 1000 m without derating; 1000...3000 m with current derating 1 % per 100 m
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: X
Environmental Disclosure: ENVPEP110706EN
Circularity Profile: ENVEOLI100203EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins