Schneider-Electric
A9N18413
Tariff code: 8536209090
Link to the manufacturers site: A9N18413 - C120H - circuit breaker - 2P - 80A - B curve
Main
Range of produc: C120
Range: Acti9
Product name: C120
Product or component type: Miniature circuit-breaker
Device short name: C120H
Device application: Distribution
Poles description: 2P
Number of protected poles: 2
Neutral position: Left
[In] rated current: 80 A at 30 °C
Network type: AC
Trip unit technology: Thermal-magnetic
Curve code: B
Breaking capacity code: H
Breaking capacity: 15000 A Icn at 230...400 V AC 50/60 Hz conforming to EN/IEC 60898-1; 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA Icu at <= 250 V DC conforming to EN/IEC 60947-2; 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
Suitability for isolation: Yes conforming to IEC 60947-2
Complementary
Network frequency: 50/60 Hz
[Ue] rated operational voltage: 380...415 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 440 V AC 50/60 Hz; <= 250 V DC; 230...400 V AC 50/60 Hz
Magnetic tripping limit: 3...5 x In
[Ics] rated service breaking capacity: 7500 A 50 % conforming to EN/IEC 60898-1 - 230...400 V AC 50/60 Hz; 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz; 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz; 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz; 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Limitation class: 3 conforming to EN/IEC 60947-2
[Ui] rated insulation voltage: 500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage: 6 kV conforming to EN/IEC 60947-2
Contact position indicator: Yes
control type: Toggle
local signalling: ON/OFF indication
Mounting mode: Clip-on
mounting support: 35 mm symmetrical DIN rail
Comb busbar and distribution block compatibility: YES
Connection pitch: 27 mm between phases
9 mm pitches: 6
height: 81 mm
Depth: 73 mm
Width: 54 mm
Net weight: 0.41 kg
Colour: White
Mechanical durability: 20000 cycles
Electrical durability: 5000 cycles conforming to IEC 60947-2
Locking options description: Handle sealable with cable diameter 0.7mm in OFF or ON position
Connections - terminals: Tunnel type terminals1…50 mm² rigid; Tunnel type terminals1.5…35 mm² flexible
Wire stripping length: 15 mm
Tightening torque: 3.5 N.m
earth-leakage protection: Separate block
Compatibility code: C120
Market segment: Residential; Small commercial
Environment
Standards: EN/IEC 60898-1; EN/IEC 60947-2
product certifications: EAC
IP degree of protection: IP20 conforming to IEC 60529
Pollution degree: 3 conforming to IEC 60947-2
Overvoltage category: IV
Tropicalisation: 2 conforming to IEC 60068-1
Relative humidity: 95 % at 55 °C
Operating altitude: 2000 m
ambient air temperature for operation: -30…60 °C
Ambient air temperature for storage: -40…70 °C
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 5.4 cm
Package 1 Width: 7.5 cm
Package 1 Length: 8.5 cm
Package 1 Weight: 388 g
Unit Type of Package 2: BB1
Number of Units in Package 2: 6
Package 2 Height: 8.5 cm
Package 2 Width: 9.5 cm
Package 2 Length: 33 cm
Package 2 Weight: 2.396 kg
Unit Type of Package 3: S03
Number of Units in Package 3: 36
Package 3 Height: 30 cm
Package 3 Width: 30 cm
Package 3 Length: 40 cm
Package 3 Weight: 14.863 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP121230EN
Circularity Profile: N/A
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins