Link to the manufacturers site: A9K23263 - miniature circuit breaker - iK60N - 2P - 63 A - B curve
Main
device application: Distribution
range: Acti 9
range of product: IK60
product name: Acti9 iK60
product or component type: Miniature circuit-breaker
device short name: IK60N
poles description: 2P
number of protected poles: 2
[In] rated current: 63 A at 30 °C
network type: AC
trip unit technology: Thermal-magnetic
curve code: B
breaking capacity: 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
suitability for isolation: Yes conforming to EN/IEC 60898-1
standards: EN/IEC 60898-1
Complementary
network frequency: 50/60 Hz
[Ue] rated operational voltage: 230 V AC 50/60 Hz
magnetic tripping limit: 3...5 x In
[Ics] rated service breaking capacity: 6000 A 100 % conforming to EN/IEC 60898-1 - 230 V AC 50/60 Hz
limitation class: 3 conforming to EN/IEC 60898-1
[Ui] rated insulation voltage: 440 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Uimp] rated impulse withstand voltage: 4 kV conforming to EN/IEC 60898-1
contact position indicator: No
control type: Toggle
local signalling: ON/OFF indication
mounting mode: Clip-on
mounting support: DIN rail
9 mm pitches: 4
height: 85 mm
width: 36 mm
depth: 78.5 mm
net weight: 200 g
colour: White
mechanical durability: 20000 cycles
electrical durability: 10000 cycles
locking options description: Padlocking device
connections - terminals: Single terminal (top or bottom) 1…35 mm² rigid
wire stripping length: 14 mm for top or bottom connection
tightening torque: 3.5 N.m top or bottom
earth-leakage protection: Without
compatibility code: IK60
Environment
IP degree of protection: IP20 conforming to IEC 60529
pollution degree: 2 conforming to EN/IEC 60898-1
overvoltage category: III
ambient air temperature for operation: -25…60 °C
ambient air temperature for storage: -40…85 °C