Schneider-Electric
34402
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: 34402 - circuit breaker Compact NS630bN - Micrologic 2.0 E - 630 A - 4 poles 4t
Main
range: ComPact
product name: ComPact NS
range of product: ComPact NS630b...1600
device short name: Compact NS630bN
product or component type: Circuit breaker
device application: Distribution
poles description: 4P
protected poles description: 4D
neutral position: Left
[In] rated current: 630 A at 50 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz
network type: AC
network frequency: 50/60 Hz
suitability for isolation: Yes conforming to EN/IEC 60947-2
utilisation category: Category B
breaking capacity: 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code: N 50 kA 415 V AC
trip unit name: Micrologic 2.0 E
trip unit technology: Electronic
trip unit protection functions: LI
control type: Toggle; Rotary handle
mounting mode: Fixed
Complementary
[Ui] rated insulation voltage: 800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage: 8 kV conforming to IEC 60947-2
[Ics] rated service breaking capacity: 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current: 19.2 kA 1 s conforming to IEC 60947-2
mechanical durability: 10000 cycles
electrical durability: 2000 cycles at 690 V In; 4000 cycles at 690 V In/2; 5000 cycles at 440 V In; 6000 cycles at 440 V In/2
power losses: 10 W
mounting support: Backplate
upside connection: Front
downside connection: Front
connection pitch: 70 mm
protection type: L : for overload protection (long time); I : for instantaneous short-circuit protection
trip unit rating: 630 A at 50 °C
long time pick-up adjustment type Ir: Adjustable 9 settings
long time pick-up adjustment range: 0.4...1 x In
long time delay adjustment type: Adjustable 9 settings
[tr] long-time delay adjustment range: 12.5…600 s at 1.5 x Ir; 0.5…24 s at 6 x Ir; 0.7…16.6 s at 7.2 x Ir
thermal memory: 20 mn
instantaneous pick-up adjustment type Ii: Adjustable
instantaneous pick-up adjustment range: 1.5...10 x Ir
earth-leakage protection: Without
neutral protection setting: No protection (3d); 0.5 x Ir (3d + N/2); 1 x Ir (4d)
zone selective interlocking ZSI: Without
auxiliary contact composition: 1 NO/NC
local signalling: 4 LEDs (red) for fault indication; 1 LED (yellow) for overload
display type: LCD display
type of measurement: Energy meter
width: 280 mm
height: 327 mm
depth: 147 mm
net weight: 18 kg
compatibility code: NS630b
Environment
standards: EN/IEC 60947-2
product certifications: ASTA; ASEFA
pollution degree: 3 conforming to IEC 60947
IP degree of protection: IP40 conforming to IEC 60529
IK degree of protection: IK07 conforming to EN 50102
ambient air temperature for operation: -25…70 °C
ambient air temperature for storage: -40…85 °C
relative humidity: 0…95 %
operating altitude: 0...2000 m without derating; 2000 m...5000 m with derating
Offer Sustainability
Sustainable offer status: Green Premium product
EU RoHS Directive: Compliant
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure: ENVPEP130103EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.