Schneider-Electric
33555
Tariff code: 8536209090
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: 33555 - circuit breaker Compact NS800N - Micrologic 5.0 - 800 A - 4 poles 4t
Main
Range: ComPact
Product name: ComPact NS
Range of product: ComPact NS630b...1600
device short name: Compact NS800N
product or component type: Circuit breaker
Device application: Distribution
Poles description: 4P
Protected poles description: 4D
Neutral position: Left
[In] rated current: 800 A at 50 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Suitability for isolation: Yes conforming to EN/IEC 60947-2
Utilisation category: Category B
Breaking capacity: 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code: N 50 kA 415 V AC
Trip unit name: MicroLogic 5.0
Trip unit technology: Electronic
Trip unit protection functions: LSI
Control type: Toggle; Rotary handle
Mounting mode: Fixed
Complementary
[Ui] rated insulation voltage: 800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage: 8 kV conforming to IEC 60947-2
[Ics] rated service breaking capacity: 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current: 19.2 kA 1 s conforming to IEC 60947-2
Mechanical durability: 10000 cycles
Electrical durability: 2000 cycles at 690 V In; 4000 cycles at 690 V In/2; 5000 cycles at 440 V In; 6000 cycles at 440 V In/2
Power losses: 15 W
Mounting support: Backplate
Upside connection: Front
downside connection: Front
Connection pitch: 70 mm
Protection type: L : for overload protection (long time); S : for short time short-circuit protection; I : for instantaneous short-circuit protection
Trip unit rating: 800 A at 50 °C
Long time pick-up adjustment type Ir: Adjustable 9 settings
long time pick-up adjustment range: 0.4...1 x In
Long time delay adjustment type: Adjustable 9 settings
[tr] long-time delay adjustment range: 12.5…600 s at 1.5 x Ir; 0.5…24 s at 6 x Ir; 0.7…16.6 s at 7.2 x Ir
Thermal memory: 20 mn
Short-time pick-up adjustment type Isd: Adjustable 9 settings
[Isd] short-time pick-up adjustment range: 1.5...10 x Ir
Short-time delay adjustment type: Adjustable
[tsd] short-time delay adjustment range: 0.1…0.4 s I²t=on; 0…0.4 s I²t=off
instantaneous pick-up adjustment type Ii: Adjustable
instantaneous pick-up adjustment range: Off; 2...15 x In
earth-leakage protection: Without
Neutral protection setting: No protection (3D); 0.5 x Ir (3D + N/2); 1 x Ir (4D)
Zone selective interlocking ZSI: Without
Auxiliary contact composition: 1 NO/NC
Local signalling: 4 LEDs (red) for fault indication; 1 LED (yellow) for overload
width: 280 mm
height: 327 mm
depth: 147 mm
net weight: 18 kg
Compatibility code: NS800
Environment
Standards: EN/IEC 60947-2
Product certifications: ASEFA; ASTA
Pollution degree: 3 conforming to IEC 60947
IP degree of protection: IP40 conforming to IEC 60529
IK degree of protection: IK07 conforming to EN 50102
Ambient air temperature for operation: -25…70 °C
Ambient air temperature for storage: -50…85 °C
Relative humidity: 0…95 %
Operating altitude: 0...2000 m without derating; 2000 m...5000 m with derating
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 30 cm
Package 1 Width: 40 cm
Package 1 Length: 60 cm
Package 1 Weight: 15.79 kg
Unit Type of Package 2: P12
Number of Units in Package 2: 15
Package 2 Height: 112 cm
Package 2 Width: 100 cm
Package 2 Length: 120 cm
Package 2 Weight: 254 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant
Mercury free: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP130103EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins