Schneider-Electric
31155
Tariff code: 8536508090
Link to the manufacturers site: 31155 - manual source changeover switch INS630 - 4 poles - 630 A
Main
Range of produc: INS320...630
Range: TransferPacT; ComPact
Device short name: INS630
Product or component type: Manual transfer switch
Device application: Change source of supply
Range compatibility: ComPact ComPacT INS INS630 switch disconnector
Poles description: 4P
Network type: DC; AC
Network frequency: 50/60 Hz
Mounting mode: Fixed
Upside connection: Front
downside connection: Front
Suitability for isolation: Yes
Contact position indicator: Yes
[Icm] rated short-circuit making capacity: 330 kA with upstream protection circuit breaker 690 V AC at 50/60 Hz; 50 kA switch-disconnector alone 690 V AC at 50/60 Hz
Complementary
transfer switch class: PC
Number of contact position: 3
control type: Direct front rotary handle
Operating mode: Manual
mounting support: Rail; Plate
Locking options description: Padlocking in OFF position
[Ie] rated operational current: AC-22A: 630 A AC 50/60 Hz 220/240 V; AC-22A: 630 A AC 50/60 Hz 380/415 V; AC-22A: 630 A AC 50/60 Hz 440/480 V; AC-22A: 630 A AC 50/60 Hz 500/525 V; AC-22A: 630 A AC 50/60 Hz 660/690 V; AC-23A: 630 A AC 50/60 Hz 220/240 V; AC-23A: 630 A AC 50/60 Hz 380/415 V; AC-23A: 630 A AC 50/60 Hz 440/480 V; AC-23A: 630 A AC 50/60 Hz 500/525 V; AC-23A: 630 A AC 50/60 Hz 660/690 V; DC-22A: 550 A DC 125 V 2 poles in series; DC-23A: 550 A DC 125 V 2 poles in series; DC-23B: 630 A DC 125 V 2 poles in series; DC-22A: 550 A DC 250 V 4 poles in series; DC-23A: 550 A DC 250 V 4 poles in series; DC-23B: 630 A DC 250 V 4 poles in series
[Ith] conventional free air thermal current: 630 A at 60 °C
Rated duty: Uninterrupted
Intermittent duty class: Class 120 - 60 %
[Ui] rated insulation voltage: 750 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 8 kV
[Ue] rated operational voltage: 690 V AC 50/60 Hz conforming to IEC 60947-3; 250 V DC conforming to IEC 60947-3
Mechanical interlocking: With mechanical interlocking
Mechanical durability: 10000 cycles
Electrical durability: AC-22A: 1500 cycles 440 V AC 50/60 Hz; AC-22A: 1500 cycles 500 V AC 50/60 Hz; AC-22A: 1500 cycles 690 V AC 50/60 Hz; AC-23A: 1500 cycles 440 V AC 50/60 Hz; AC-23A: 1500 cycles 500 V AC 50/60 Hz; AC-23A: 1500 cycles 690 V AC 50/60 Hz; DC-23A: 1000 cycles 250 V DC 4 poles in series; DC-23B: 200 cycles 250 V DC 4 poles in series
Connection pitch: 45 mm
[Icw] rated short-time withstand current: 11.5 kA during 3 s conforming to IEC 60947-3; 20 kA during 1 s conforming to IEC 60947-3; 4 kA during 30 s conforming to IEC 60947-3; 4.9 kA during 20 s conforming to IEC 60947-3
height: 205 mm
Width: 395 mm
Depth: 155 mm
Net weight: 13.5 kg
Compatibility code: ONE_PIECE_CHANGEOVER_INS630
Environment
Standards: IEC 60947-3; IEC 60947-1
product certifications: CB
Electrical shock protection class: Class II
IP degree of protection: IP40 conforming to IEC 60947-3
Pollution degree: 3
ambient air temperature for operation: -25…70 °C
Ambient air temperature for storage: -50…85 °C
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 21.2 cm
Package 1 Width: 22 cm
Package 1 Length: 49.4 cm
Package 1 Weight: 14.596 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant with Exemptions
Mercury free: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP1304027
Circularity Profile: ENVEOLI1304027
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins