Schneider-Electric
29600
Tariff code:
This product is discontinued.
This product is no longer manufactured, but we have it in stock. Please contact us for price and delivery information!
Link to the manufacturers site: 29600 - circuit breaker Compact NS100N - TMD - 100 A - 2 poles 2d
Main
range: ComPact
range of product: Compact NS100...630
product or component type: Circuit breaker
product name: ComPact NS
device short name: Compact NS100N
circuit breaker name: Compact NS100N
device application: Distribution
poles description: 2P
protected poles description: 2t
network type: DC; AC
network frequency: 50/60 Hz
[In] rated current: 100 A at 40 °C; 100 A at 65 °C
[Ui] rated insulation voltage: 750 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage: 8 kV conforming to IEC 60947-2
[Ue] rated operational voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2; 750 V DC conforming to IEC 60947-2
breaking capacity code: N
breaking capacity: 85 kA Icu at 250 V DC 1P conforming to IEC 60947-2; 85 kA Icu at 48/125 V DC 1P conforming to IEC 60947-2; 10 kA at 600 V AC 50/60 Hz conforming to NEMA AB1 HIC; 25 kA at 480 V AC 50/60 Hz conforming to NEMA AB1 HIC; 85 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 HIC; 18 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 18 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA Icu at 220 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA Icu at 500 V DC 2P conforming to IEC 60947-2
[Ics] rated service breaking capacity: 85 kA at 250 V DC conforming to IEC 60947-2; 85 kA at 48/125 V DC conforming to IEC 60947-2; 18 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 18 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA at 220 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA at 500 V DC conforming to IEC 60947-2
suitability for isolation: Yes conforming to IEC 60947-2
utilisation category: Category A
trip unit name: TM-D
trip unit technology: Thermal-magnetic
trip unit rating: 100 A
protection type: Short-circuit protection (magnetic); Overload protection (thermal)
pollution degree: 3 conforming to IEC 60947
Complementary
control type: Toggle
mounting mode: Fixed
mounting support: Backplate
upside connection: Front
downside connection: Front
mechanical durability: 20000 cycles
electrical durability: 10000 cycles 277 V AC 50/60 Hz In conforming to IEC 60947-2; 20000 cycles 277 V AC 50/60 Hz In/2 conforming to IEC 60947-2
connection pitch: 35 mm
local signalling: Positive contact indication
magnetic tripping current: 300 A; 800 A; 1250 A; 190 A; 260 A; 500 A; 640 A; 1000 A
long time pick-up adjustment type Ir: Fixed
long time pick-up adjustment range: 0.8...1 x In
instantaneous pick-up adjustment type Ii: Fixed
instantaneous pick-up adjustment range: 800 A
height: 161 mm
width: 70 mm
depth: 86 mm
compatibility code: NS100
Environment
standards: IEC 60947-2
product certifications: ASEFA; LCIE; KEMA; ASTA
IP degree of protection: IP40 conforming to IEC 60529
IK degree of protection: IK07 conforming to EN 50102
ambient air temperature for operation: -25…70 °C
ambient air temperature for storage: -50…85 °C
Offer Sustainability
Sustainable offer status: Green Premium product
EU RoHS Directive: Compliant
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure: ENVPEP050905EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins