Schneider-Electric
METSEPM5761
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: METSEPM5761 - PM5761, PANEL MOUNT, WC+SS RCM MID
Main
range: PowerLogic
product name: PowerLogic PM5000
device short name: PM5761
product or component type: Power meter
market segment: Buildings small building cost management: billing: main incomer; Buildings small building cost management: billing: sub feeder; Buildings medium building cost management: billing: main incomer; Buildings medium building cost management: billing: sub feeder; Buildings large building cost management: billing: main incomer; Buildings large building cost management: billing: sub feeder; Buildings multi-site cost management: billing: main incomer; Buildings multi-site cost management: billing: sub feeder; Data center cost management: billing: main incomer; Data center cost management: billing: sub feeder; Healthcare cost management: billing: main incomer; Healthcare cost management: billing: sub feeder; Industry cost management: billing: main incomer; Industry cost management: billing: sub feeder; Buildings small building cost management: cost allocation: main incomer; Buildings small building cost management: cost allocation: sub feeder; Buildings medium building cost management: cost allocation: main incomer; Buildings medium building cost management: cost allocation: sub feeder; Buildings large building cost management: cost allocation: main incomer; Buildings large building cost management: cost allocation: sub feeder; Buildings multi-site cost management: cost allocation: main incomer; Buildings multi-site cost management: cost allocation: sub feeder; Data center cost management: cost allocation: main incomer; Data center cost management: cost allocation: sub feeder; Healthcare cost management: cost allocation: main incomer; Healthcare cost management: cost allocation: sub feeder; Industry cost management: cost allocation: main incomer; Industry cost management: cost allocation: sub feeder; Buildings small building network management: main incomer; Buildings small building network management: sub feeder; Buildings medium building network management: main incomer; Buildings medium building network management: sub feeder; Buildings large building network management: sub feeder; Buildings multi-site network management: sub feeder; Data center network management: sub feeder; Healthcare network management: sub feeder; Industry network management: sub feeder
Complementary
power quality analysis: up to the 63rd harmonic; waveform capture; voltage sag and swell detection; residual current monitoring
metering type: Measured neutral current; Calculated ground current; Residual current I0
device application: Gateway; WAGES metering; Power monitoring; Multi-tariff
type of measurement: Current; Voltage; Frequency; Power factor; Energy; Active and reactive power
[Us] rated supply voltage: 125...250 V DC; 100...480 V AC 45...65 Hz
network frequency: 60 Hz; 50 Hz
[In] rated current: 1 A; 5 A
poles description: 3P + N; 3P; 1P + N
maximum power consumption in VA: 10 VA at 480 V
ride-through time: 35 ms 120 V AC typical; 129 ms 230 V AC typical
display type: Backlit LCD
display resolution: 128 x 128 pixels
sampling rate: 128 samples/cycle
measurement current: 5…10000 mA
analogue input type: Voltage (impedance 5 MOhm); Current (impedance 0.3 mOhm)
measurement voltage: 20…400 V AC 45...65 Hz between phase and neutral; 20…690 V AC 45...65 Hz between phases
frequency measurement range: 45…65 Hz
number of inputs: 4 digital
measurement accuracy: Apparent power +/- 0.5 %; Frequency +/- 0.05 %; Active energy +/- 0.2 %; Reactive energy +/- 1 %; Active power +/- 0.2 %; Voltage +/- 0.1 %; Power factor +/- 0.005; Current +/- 0.15 °C
accuracy class: Class 0.2S active energy conforming to IEC 62053-22
number of outputs: 2 digital
information displayed: Tariff (8)
communication port protocol: Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500 V; JBUS; Modbus TCP/IP at 10/100 Mbit/s, insulation 2500 V; Ethernet Modbus TCP/IP daisy chain; BACnet IP
communication port support: RS485; Ethernet
communication gateway: Ethernet/serial
data recording: Event logs; Maintenance logs; Min/max of instantaneous values; Data logs; Alarm logs; Time stamping
memory capacity: 1.1 MB
web services: Alarm notification by e-mail; Web server; Diagnostic via predefined web pages; Real time viewing of data
Ethernet service: SNTP client; SNMP-Traps
connections - terminals: Voltage circuit: screw terminal block4; Control circuit: screw terminal block2; Current transformer: screw terminal block6; RS485 link: screw terminal block4; Digital input: screw terminal block8; Digital output: screw terminal block4; Ethernet network: RJ45 connector2
mounting mode: Flush-mounted
mounting support: Framework
standards: EN 50470-3; IEC 61557-12; IEC 62053-22; IEC 62053-24; IEC 60529; EN 50470-1; UL 61010-1
product certifications: CE conforming to IEC 61010-1; CULus conforming to UL 61010-1; MID conforming to EN 50470-1; MID conforming to EN 50470-3
width: 96 mm
depth: 72 mm
height: 96 mm
net weight: 450 g
Environment
electromagnetic compatibility: Limits for harmonic current emissions class A conforming to IEC 61000-3-2; Conducted RF disturbances level 3 conforming to IEC 61000-4-6; Magnetic field at power frequency level 4 conforming to IEC 61000-4-8; Conducted and radiated emissions class B conforming to EN 55022; Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3; Electrostatic discharge - test level: 8 kV level 4 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; Surge immunity test level 4 conforming to IEC 61000-4-5; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
IP degree of protection: IP52 front: conforming to IEC 60529; IP30 body: conforming to IEC 60529
relative humidity: 5…95 % at 50 °C
pollution degree: 2
ambient air temperature for operation: -25…70 °C
ambient air temperature for storage: -40…85 °C
operating altitude: 3000 m
compatibility code: PM5761
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: X
Environmental Disclosure: ENVPEP1310016EN
Circularity Profile: ENVEOLI1310016EN