Skip to main content

Schneider-Electric
XMLA001R2S11

pressure switch XMLA 1 bar - fixed scale 1 threshold - 1 C/O
Barcode: 3389110746716
Tariff code: 9032200090

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: XMLA001R2S11 - pressure switch XMLA 1 bar - fixed scale 1 threshold - 1 C/O

Main

Range of produc: Telemecanique Pressure sensors XM

Product or component type: Electromechanical pressure sensor

Pressure sensor type: Electromechanical pressure sensor

Device short name: XMLA

Pressure rating: 1 bar

Controlled fluid: Air (0…160 °C); Hydraulic oil (0…160 °C)

Fluid connection type: G 1/4 (female) conforming to ISO 228

Electrical connection: Screw-clamps terminals, 1 x 0.5...2 x 2.5 mm²; 1 connector Pg 13

AWG gauge: AWG 20...AWG 14

Cable entry: Cable gland 9…13 mm

Contacts type and composition: 1 C/O

Product specific application: -

Pressure switch type of operation: Detection of 1 single threshold

Electrical circuit type: Control circuit

Scale type: Fixed differential

Local display: With

Adjustable range of switching point on rising pressure: 0.03…1 bar

Adjustable range of switching point on falling pressure: 0.01…0.96 bar

Maximum permissible accidental pressure: 2.25 bar

Destruction pressure: 4.5 bar

Pressure actuator: Diaphragm

Materials in contact with fluid: Steel; FPM, FKM; 304L stainless steel

Enclosure material: Zinc alloy

[In] rated current: 3 A, B300, AC-15 (Ue = 120 V) conforming to EN/IEC 60947-5-1; 1.5 A, B300, AC-15 (Ue = 240 V) conforming to EN/IEC 60947-5-1; 0.1 A, R300, DC-13 (Ue = 250 V) conforming to EN/IEC 60947-5-1

Complementary

Natural differential at low setting: 0.02 bar (+/- 0.01 bar)

Natural differential at high setting: 0.04 bar (+/- 0.01 bar)

Maximum permissible pressure - per cycle: 1.25 bar

Terminal block type: 4 terminals

Maximum operating rate: 120 cyc/mn

Repeat accuracy: 2 %

[Ui] rated insulation voltage: 300 V conforming to UL 508; 500 V conforming to EN/IEC 60947-1; 300 V conforming to CSA C22.2 No 14

[Uimp] rated impulse withstand voltage: 6 kV conforming to EN/IEC 60947-1

Auxiliary contacts operation: Snap action

Contacts material: Silver contacts

Maximum resistance across terminals: 25 mOhm conforming to IEC 255-7 category 3; 25 mOhm conforming to NF C 93-050 method A

Short-circuit protection: 10 A cartridge fuse, type gG (gl)

Mechanical durability: 4000000 cycles

Setting: External

Terminals description ISO n°1: (13-14-11-12)OF

height: 162 mm

Depth: 110 mm

Width: 110 mm

Net weight: 2.555 kg

Controlled fluid: Air,hydraulic oil

Temperature of controlled fluid: 0…160 °C

Environment

Standards: UL 508; CSA C22.2 No 14; EN/IEC 60947-5-1; CE

product certifications: UL; BV; CCC; EAC; LROS (Lloyds register of shipping); CSA

Protective treatment: TC standard version

ambient air temperature for operation: -25…70 °C

Ambient air temperature for storage: -40…70 °C

Operating position: Any position

Vibration resistance: 2 gn conforming to IEC 60068-2-6 (f = 30…500 Hz)

Shock resistance: 30 gn conforming to IEC 60068-2-27

Electrical shock protection class: Class I conforming to IEC 1140; Class I conforming to IEC 536; Class I conforming to NF C 20-030

IP degree of protection: IP66 conforming to EN/IEC 60529

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 15.600 cm

Package 1 Width: 15.800 cm

Package 1 Length: 16.200 cm

Package 1 Weight: 2.406 kg

Unit Type of Package 2: P06

Number of Units in Package 2: 24

Package 2 Height: 75.000 cm

Package 2 Width: 60.000 cm

Package 2 Length: 80.000 cm

Package 2 Weight: 70.696 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free: Yes

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP110914EN

Circularity Profile: N/A

© 2018 Alplan Kft.