Schneider-Electric
TM3TM3
Tariff code: 8538909999
Link to the manufacturers site: TM3TM3 - module TM3 - 2 temperature inputs and 1 analog output
Main
Range of product: Modicon TM3
product or component type: Input/output analog module
Range compatibility: Modicon M221; Modicon M241; Modicon M251; Modicon M262
Analogue input number: 2
Analogue input type: current 4...20 mA; current 0...20 mA; voltage 0...10 V; voltage - 10...10 V; thermocouple - 200...1000 °C with thermocouple J; thermocouple - 200...1300 °C with thermocouple K; thermocouple 0...1760 °C with thermocouple R; thermocouple 0...1760 °C with thermocouple S; thermocouple 0...1820 °C with thermocouple B; thermocouple - 200...400 °C with thermocouple T; thermocouple - 200...1300 °C with thermocouple N; thermocouple - 200...800 °C with thermocouple E; thermocouple 0...2315 °C with thermocouple C; Ni 100/Ni 1000 temperature probe - 60...180 °C; Pt 100 temperature probe - 200...850 °C; Pt 1000 temperature probe - 200...600 °C
Analogue output number: 1
Analogue output type: Current: 4...20 mA; Current: 0...20 mA; Voltage: 0...10 V; Voltage: - 10...10 V
Complementary
Analogue input resolution: 16 bits; 15 bits + sign
Permissible continuous overload: 13 V, analogue input type: voltage; 40 mA, analogue input type: current
Input impedance: <= 50 Ohm current; >= 1 MOhm voltage; >= 1 MOhm thermocouple; >= 1 MOhm temperature probe
Analogue output resolution: 12 bits
LSB value: 0.15 mV 0...10 Vvoltage; 0.30 mV - 10...10 Vvoltage; 0.30 µA 0...20 mAcurrent; 0.244 µA 4...20 mAcurrent; 0.1 °Ctemperature probe; 0.1 °Cthermocouple; 2.44 mV 0...10 V voltage; 4.88 mV - 10...10 V voltage; 4.88 µA 0...20 mA current; 3.91 µA 4...20 mA current
Load type: Resistive
Load impedance ohmic: 1 kOhm voltage; 300 Ohm current
Stabilisation time: 1 ms
Conversion time: 100 ms + 100 ms per channel + 1 controller cycle time for analogue input thermocouple; 100 ms + 100 ms per channel + 1 controller cycle time for analogue input temperature probe; 10 ms + 10 ms per channel + 1 controller cycle time for analogue input voltage/current
Sampling duration: 10 ms, analogue input type: voltage/current; 100 ms, analogue input type: voltage/current; 100 ms, analogue input type: thermocouple; 100 ms, analogue input type: temperature probe
Absolute accuracy error: +/- 6 °C at 25 °C for thermocouple R, S 0...200 °C; +/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C; +/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C; +/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C; +/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C; +/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C; +/- 0.1 % of full scale at 25 °C for analogue input voltage/current; +/- 0.1 % of full scale at 25 °C for thermocouple C 0...2315 °C; +/- 0.1 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe; +/- 0.1 % of full scale at 25 °C for thermocouple R, S 200...1760 °C; +/- 0.1 % of full scale at 25 °C for thermocouple B 300...1820 °C; +/- 0.1 % of full scale at 25 °C for thermocouple K 0...1300 °C; +/- 0.1 % of full scale at 25 °C for thermocouple J 0...1000 °C; +/- 0.1 % of full scale at 25 °C for thermocouple E 0...800 °C; +/- 0.1 % of full scale at 25 °C for thermocouple T 0...400 °C; +/- 0.1 % of full scale at 25 °C for thermocouple N 0...1300 °C; +/- 0.1 % of full scale at 25 °C for analogue output voltage/current
Temperature drift: +/- 0.006 %FS/°C
Repeat accuracy: +/-0.5 %FS for input; +/- 0.4 %FS for output
Non-linearity: +/- 0.01 %FS, analogue output type: analog output; +/- 0.1 %FS, analogue input type: analog input
Output ripple: 20 mV
Cross talk: <= 1 LSB
[Us] rated supply voltage: 24 V DC
Supply voltage limits: 20.4…28.8 V
Type of cable: Twisted shielded pairs cable <30 m for input/output circuit
Current consumption: 55 mA at 24 V DC via external supply no load; 55 mA at 5 V DC via bus connector no load; 60 mA at 5 V DC via bus connector full load; 80 mA at 24 V DC via external supply full load
Local signalling: 1 LED (green) for PWR
Electrical connection: 11 x 2.5 mm² removable screw terminal block with pitch 5.08 mm adjustment for inputs, outputs and supply
Insulation: Between input and supply at 1500 V AC; Between input and internal logic at 500 V AC; Between output and supply at 1500 V AC; Between output and internal logic at 500 V AC
Marking: CE
Surge withstand: 1 kV power supply common mode conforming to IEC 61000-4-5; 0.5 kV power supply differential mode conforming to IEC 61000-4-5; 1 kV I/O common mode conforming to IEC 61000-4-5; 0.5 kV I/O differential mode conforming to IEC 61000-4-5
Mounting support: Top hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; plate or panel with fixing kit
Height: 90 mm
Depth: 70 mm
Width: 23.6 mm
Net weight: 0.115 kg
Environment
Standards: IEC 61131-2
Product certifications: CE; UKCA; RCM; EAC; cULus; cULus HazLoc
Resistance to electrostatic discharge: 8 kV in air conforming to IEC 61000-4-2; 4 kV on contact conforming to IEC 61000-4-2
Resistance to electromagnetic fields: 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3; 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3; 1 V/m 2 GHz...3 GHz conforming to IEC 61000-4-3
Resistance to magnetic fields: 30 A/m conforming to IEC 61000-4-8
Resistance to fast transients: 1 kV (I/O) conforming to IEC 61000-4-4
Resistance to conducted disturbances: 10 V 0.15...80 MHz conforming to IEC 61000-4-6; 3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission: Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to IEC 55011; Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to IEC 55011
Immunity to microbreaks: 10 ms
Ambient air temperature for operation: -10…55 °C horizontal installation; -10…35 °C vertical installation
Ambient air temperature for storage: -25…70 °C
Relative humidity: 10…95 %, without condensation (in operation); 10…95 %, without condensation (in storage)
IP degree of protection: IP20
Pollution degree: 2
Operating altitude: 0...2000 m
Storage altitude: 0…3000 m
Vibration resistance: 3.5 mm at 5…8.4 Hz on DIN rail; 3 gn at 8.4…150 Hz on DIN rail
Shock resistance: 15 gn for 11 ms
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 7.611 cm
Package 1 Width: 10.688 cm
Package 1 Length: 12.753 cm
Package 1 Weight: 220.0 g
Unit Type of Package 2: S04
Number of Units in Package 2: 42
Package 2 Height: 30 cm
Package 2 Width: 40 cm
Package 2 Length: 60 cm
Package 2 Weight: 10.421 kg
Unit Type of Package 3: P12
Number of Units in Package 3: 504
Package 3 Height: 105 cm
Package 3 Width: 120 cm
Package 3 Length: 80 cm
Package 3 Weight: 130 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free: Yes
Mercury free: Yes
China RoHS Regulation: X
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP1402009EN
Circularity Profile: ENVEOLI1402009EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins