Schneider-Electric
18708
Tariff code: 8536201090
Link to the manufacturers site: 18708 - NG125 - circuit breaker - NG125H - 1P - 25A - C curve
Main
Range of produc: NG125
Range: Acti9
Product name: Acti9 NG125
Product or component type: Miniature circuit-breaker
Device short name: NG125H
Device application: Distribution
Poles description: 1P
Number of protected poles: 1
[In] rated current: 25 A at 40 °C
Network type: AC; DC
Trip unit technology: Thermal-magnetic
Curve code: C
Breaking capacity code: H
Breaking capacity: 36 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 36 kA Icu at 12 V DC conforming to EN/IEC 60947-2; 70 kA Icu at 110...130 V AC 50/60 Hz conforming to EN/IEC 60947-2; 36 kA Icu at 125 V DC conforming to EN/IEC 60947-2; 25 kA Icu at <= 144 V DC conforming to EN/IEC 60947-2; 9 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Utilisation category: Category A conforming to IEC 60947-2
Suitability for isolation: Yes conforming to IEC 60947-2
Complementary
Network frequency: 50/60 Hz
[Ue] rated operational voltage: 380...415 V AC 50/60 Hz; 125 V DC; <= 144 V DC; 12 V DC; 220...240 V AC 50/60 Hz; 110...130 V AC 50/60 Hz
Magnetic tripping limit: 8 x In +/- 20 %
[Ics] rated service breaking capacity: 52.5 kA 75 % conforming to EN/IEC 60947-2 - 110...130 V AC 50/60 Hz; 27 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz; 6.75 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz; 36 kA 100 % conforming to EN/IEC 60947-2 - 60 V DC; 36 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC
[Ui] rated insulation voltage: 690 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage: 8 kV conforming to EN/IEC 60947-2
Contact position indicator: Yes
control type: Toggle; Manual tripping test
local signalling: Trip indicator; ON/OFF indication
Mounting mode: Clip-on
mounting support: 35 mm symmetrical DIN rail
Mounting position: Vertical
Connection pitch: 27 mm between devices
Comb busbar and distribution block compatibility: YES
9 mm pitches: 3
height: 103 mm
Depth: 81 mm
Width: 27 mm
Net weight: 0.24 kg
Mechanical durability: 20000 cycles
Electrical durability: 10000 cycles
Provision for padlocking: Padlockable
Locking options description: Integrated padlocking
Connections - terminals: Tunnel type terminals1.5…50 mm² rigid; Tunnel type terminals1…35 mm² flexible
Wire stripping length: 20 mm
Tightening torque: 3.5 N.m
earth-leakage protection: Without
Compatibility code: NG125
Market segment: Small commercial; Small buildings
Environment
Standards: EN/IEC 60947-2
IP degree of protection: IP20 conforming to IEC 60529
IK degree of protection: IK05 conforming to EN/IEC 62262
Pollution degree: 3 conforming to IEC 60947-2
Overvoltage category: IV
Tropicalisation: 2 conforming to IEC 60068-1
Relative humidity: 95 % at 55 °C
ambient air temperature for operation: -30…70 °C
Ambient air temperature for storage: -40…70 °C
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 3.2 cm
Package 1 Width: 8.3 cm
Package 1 Length: 10.8 cm
Package 1 Weight: 237.0 g
Unit Type of Package 2: BB1
Number of Units in Package 2: 12
Package 2 Height: 9.1 cm
Package 2 Width: 11.9 cm
Package 2 Length: 36.0 cm
Package 2 Weight: 3.019 kg
Unit Type of Package 3: S03
Number of Units in Package 3: 72
Package 3 Height: 30.0 cm
Package 3 Width: 30.0 cm
Package 3 Length: 40.0 cm
Package 3 Weight: 18.601 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP1406008EN
Circularity Profile: ENVEOLI1406008_V1
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.