Schneider-Electric
LC1E630F7
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: LC1E630F7 - EasyPact TVS contactor 3P(3 NO) - AC-3 - <= 440 V 630A - 110 V AC coil
Main
range: EasyPact
product name: EasyPact TVS
product or component type: Contactor
device short name: LC1E
contactor application: Resistive load; Motor control
utilisation category: AC-1; AC-3
poles description: 3P
pole contact composition: 3 NO
[Ue] rated operational voltage: Power circuit: <= 690 V AC 50/60 Hz
[Ie] rated operational current: 630 A (at <55 °C) at <= 440 V AC AC-3 for power circuit; 1000 A (at <55 °C) at <= 440 V AC AC-1 for power circuit
motor power kW: 185 kW at 220...230 V AC 50/60 Hz; 335 kW at 380...400 V; 375 kW at 415 V; 400 kW at 440 V; 400 kW at 500 V; 450 kW at 660...690 V
control circuit type: AC at 50/60 Hz
[Uc] control circuit voltage: 110 V AC 50/60 Hz
height: 464 mm
width: 309 mm
depth: 255 mm
net weight: 18.6 kg
Complementary
[Uimp] rated impulse withstand voltage: 8 kV coil not connected to the power circuit conforming to IEC 60947
[Ui] rated insulation voltage: 690 V conforming to IEC 60947-4-1
overvoltage category: III
[Ith] conventional free air thermal current: 1000 A (at 40 °C) for power circuit
Irms rated making capacity: 6300 A at 440 V AC for power circuit conforming to IEC 60947-4-1
rated breaking capacity: 5040 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current: 5050 A 40 °C - 10 s for power circuit
associated fuse rating: 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1; 800 A gG at <= 690 V coordination type 1 for power circuit
average impedance: 0.12 mOhm - Ith 1000 A 50 Hz for power circuit
power dissipation per pole: 48 W AC-3; 120 W AC-1
control circuit voltage limits: Operational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C); Drop-out: 0.25...0.5 Uc at 50/60 Hz (at <55 °C)
operating time: 40...80 ms on closing; 100...200 ms on opening
mechanical durability: 400000 cycles
maximum operating rate: 1200 cyc/h 55 °C
inrush power in VA: 1650 VA 50 Hz cos phi 0.9 (at 20 °C); 1650 VA 60 Hz cos phi 0.9 (at 20 °C)
hold-in power consumption in VA: 22 VA 50 Hz cos phi 0.9 (at 20 °C); 22 VA 60 Hz cos phi 0.9 (at 20 °C)
heat dissipation: 20 W for control circuit; 20 W
minimum switching current: 5 mA for control circuit
minimum switching voltage: 17 V for control circuit
non-overlap time: 1.5 ms on energisation guaranteed between NC and NO contact; 1.5 ms on de-energisation guaranteed between NC and NO contact
insulation resistance: > 10 MOhm for control circuit
electrical durability: 200000 cycles AC-1; 600000 cycles AC-3
mounting support: Plate
connections - terminals: Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end; Power circuit: cable with lug 2; Power circuit: bars 2 - busbar cross section: 60 x 5 mm
tightening torque: Control circuit: 1.2 N.m; Power circuit: 58 N.m
Environment
standards: IEC 60947-5-1; IEC 60947-1; IEC 60947-4-1
product certifications: EAC; CE
IP degree of protection: IP00 conforming to IEC 60529
pollution degree: 3
ambient air temperature for operation: -5…55 °C
ambient air temperature for storage: -60…80 °C
permissible ambient air temperature around the device: -20…70 °C at Uc
operating altitude: 3000 m without derating
fire resistance: 850 °C conforming to IEC 60695-2-1
mechanical robustness: Shocks contactor open: 6 Gn for 11 ms; Shocks contactor closed: 15 Gn for 11 ms; Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 4 Gn, 5...300 Hz
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure: ENVPEP1406035EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.