Skip to main content

Schneider-Electric
16970

residual current circuit breaker ID - 2 poles - 125 A - class A 30 mA
Barcode: 3303430169703
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: 16970 - residual current circuit breaker ID - 2 poles - 125 A - class A 30 mA

Main

range of product: ID RCCB

range: Acti 9

product name: Acti9 RCCB-ID

product or component type: Residual current circuit breaker (RCCB)

device short name: RCCB-ID

poles description: 2P

neutral position: Left

[In] rated current: 125 A

network type: AC

earth-leakage sensitivity: 30 mA

earth-leakage protection time delay: Instantaneous

earth-leakage protection class: Type A

rated breaking and making capacity: Im = 1250 A 230 V conforming to IEC 61008

rated conditional short-circuit current: Inc 10 kA 125 A

Complementary

device location in system: Outgoer

network frequency: 50/60 Hz

[Ue] rated operational voltage: 230 V AC 50 Hz conforming to IEC 61008

residual current tripping technology: Electromechanical

[Ui] rated insulation voltage: 440 V AC 50 Hz conforming to IEC 61008-1

[Uimp] rated impulse withstand voltage: 4 kV conforming to IEC 61008-1

control type: Toggle

mounting mode: Fixed

mounting support: 35 mm symmetrical DIN rail

9 mm pitches: 4

height: 86 mm

width: 36 mm

depth: 76 mm

net weight: 230 g

colour: Grey

mechanical durability: 5000 cycles

electrical durability: 2000 cycles

provision for padlocking: Padlockable

connections - terminals: Tunnel type terminals2 cable(s) 1.5…16 mm² flexible; Tunnel type terminals2 cable(s) 1.5…16 mm² rigid; Tunnel type terminals1 cable(s) 1.5…50 mm² rigid; Tunnel type terminals1 cable(s) 1.5…35 mm² flexible; Tunnel type terminals1 cable(s) 1.5…35 mm² flexible with ferrule; Tunnel type terminals2 cable(s) 1.5…16 mm² flexible with ferrule

wire stripping length: 11 mm

tightening torque: 3 N.m

compatibility code: ID_RCCB

market segment: Small commercial

Environment

standards: IEC 61008; IEC 60947-1; IEC 60947-3

IP degree of protection: IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529

pollution degree: 3

tropicalisation: 2 conforming to IEC 61008

relative humidity: 95 % at 55 °C

operating altitude: 2000 m

ambient air temperature for operation: -25…40 °C

ambient air temperature for storage: -40…85 °C

Offer Sustainability

REACh Regulation: Free of Substances of Very High Concern above the threshold

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation:  Pro-active China RoHS declaration (out of China RoHS legal scope)

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

© 2018 Alplan Kft.