Schneider-Electric
KNT100ED4306
Tariff code: 8536900100
Link to the manufacturers site: KNT100ED4306 - STRAIGHT LENGTH 100 A
Main
Range: Canalis
Range of produc: Canalis
Product name: KN
Product or component type: Straight length
Device short name: KNT
Device application: Low power distribution
[Ie] rated operational current: 100 A at 35 °C
busbar trunking polarity: 3L + PEN; 3L + N + PE
Number of tap-off outlets: 6
Length: 3 m
Complementary
[Ue] rated operational voltage: 230...500 V
Network frequency: 50/60 Hz
[Uimp] rated impulse withstand voltage: 6 kV
[Ui] rated insulation voltage: 500 V
[Icw] rated short-time withstand current: 1.4 kA
[Ipk] rated peak withstand current: 14 kA
Electrical connection: Lubricated sliding contact
Radiated magnetic field: 0.106 µT
Thermal stress limit: 1980 kA².s
THDI: 0…15 % 100 A; 15…33 % 80 A; 33…100 % 63 A
Maximum voltage drop: <0.191 V with power factor = 1 at 50 Hz with 1A for 100 m long; <0.181 V with power factor = 0.9 at 50 Hz with 1A for 100 m long; <0.165 V with power factor = 0.8 at 50 Hz with 1A for 100 m long; <0.149 V with power factor = 0.7 at 50 Hz with 1A for 100 m long
Linear resistance: 1.7 mΩ/m R20 20 °C phase conductor; 2.2 mΩ/m R1 35 °C at Inc and 50 Hz phase conductor; 0.25 mΩ/m X1 35 °C at Inc and 50 Hz phase conductor; 2.235 mΩ/m Z1 35 °C at Inc and 50 Hz phase conductor; 1.09 mΩ/m 20 °C protective conductor; 6.93 mΩ/m R0 20 °C symmetrical components method Ph/N; 1.56 mΩ/m X0 20 °C symmetrical components method Ph/N; 7.11 mΩ/m Z0 20 °C symmetrical components method Ph/N; 5.15 mΩ/m R0 20 °C symmetrical components method Ph/PE; 1.68 mΩ/m X0 20 °C symmetrical components method Ph/PE; 5.42 mΩ/m Z0 20 °C symmetrical components method Ph/PE; 3.4 mΩ/m Rb0 20 °C impedance method Ph/Ph; 3.4 mΩ/m Rb0 20 °C impedance method Ph/N; 2.85 mΩ/m Rb0 20 °C impedance method Ph/PE; 4.09 mΩ/m Rb1 35 °C at Inc with impedance method Ph/Ph; 4.09 mΩ/m Rb1 35 °C at Inc with impedance method Ph/N; 3.27 mΩ/m Rb1 35 °C at Inc with impedance method Ph/PE; 0.52 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/Ph; 0.78 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/N; 0.96 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/PE
Mounting mode: By screws
Neutral position: Up
Number of circuits: 1
control type: Communicating
Standards: IEC 61439-6
Width: 92 mm
Depth: 27.5 mm
Colour: White (RAL 9001)
Net weight: 6.7 kg
Environment
IP degree of protection: IP55 conforming to IEC 60529
IK degree of protection: IK08 conforming to IEC 62262
Ambient air temperature for operation: 0…35 °C (100 % of In); 35…40 °C (97 % of In); 40…45 °C (94 % of In); 45…50 °C (91 % of In); 50…55 °C (87 % of In)
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 3.500 cm
Package 1 Width: 10.000 cm
Package 1 Length: 310.000 cm
Package 1 Weight: 5.000 kg
Unit Type of Package 2: BB1
Number of Units in Package 2: 4
Package 2 Height: 11.000 cm
Package 2 Width: 16.000 cm
Package 2 Length: 314.000 cm
Package 2 Weight: 22.000 kg
Unit Type of Package 3: PAL
Number of Units in Package 3: 48
Package 3 Height: 44.000 cm
Package 3 Width: 64.000 cm
Package 3 Length: 320.000 cm
Package 3 Weight: 286.000 kg
Offer Sustainability
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
RoHS exemption information: Yes
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Halogen content performance: Halogen free product
© 2018 Alplan Kft.