Main

Range of produc: Harmony Analog

Product or component type: Converter for thermocouples

Analogue input type: Thermocouple 0...1200 °C/32...2192 °F thermocouple K conforming to IEC 60584

Analogue output type: Current 0...20 mA <= 500 Ohm; Current 4...20 mA <= 500 Ohm; Voltage 0...10 V >= 100 kOhm

Complementary

Protection type: Overvoltage protection on output (+/- 30 V); Reverse polarity protection on output; Short-circuit protection on output

Analogue output voltage: -15...-11 V when no input or input wire broken; 11...15 V when no input or input wire broken

Analogue output current: -30…0 mA when no input or input wire broken

[Us] rated supply voltage: 24 V DC +/- 20 %, non isolated

Current consumption: <= 40 mA for voltage; <= 40 mA for voltage output; <= 60 mA for current

Local signalling: LED (green) for power ON

Measurement error: +/- 10 % of full scale at 20 °C (electromagnetic interference of 10 V/m); +/- 1 % of full scale at 20 °C

Repeat accuracy: +/- 0.25 % full scale at 20 °C; +/- 0.8 % full scale at 60 °C

Temperature coefficient: 200 ppm/°C

Cold junction compensation: Built-in, measurement: between 0 and 60 °C

clamping connection capacity: 2 x 1.5 mm²; 1 x 2.5 mm²

Tightening torque: 0.6…1.1 N.m

Marking: CE

Surge withstand: 0.5 kV during 1.2/50 µs conforming to IEC 61000-4-5

[Ui] rated insulation voltage: 2 kV

Fixing mode: By screws (mounting plate); Clip-on (35 mm symmetrical DIN rail)

Safety reliability data: MTTFd = 49.2 years; B10d = 45447

Net weight: 0.12 kg

Environment

Standards: IEC 60584-1; IEC 60947-1

product certifications: GL; UL; CSA

IP degree of protection: IP20 (terminal block); IP50 (housing)

Fire resistance: 850 °C conforming to IEC 60695-2-1; 850 °C conforming to UL

Shock resistance: 50 gn for 11 ms conforming to IEC 60068-2-27

Vibration resistance: 5 gn (f= 10…100 Hz) conforming to IEC 60068-2-6

Resistance to electrostatic discharge: 6 kV (in contact) conforming to IEC 61000-4-2 level 3; 8 kV (in air) conforming to IEC 61000-4-2 level 3

Resistance to fast transients: 1 kV (on input-output) conforming to IEC 61000-4-4; 2 kV (on power supply) conforming to IEC 61000-4-4

Disturbance radiated/conducted: CISPR 11; CISPR 22 group 1 - class B

Ambient air temperature for storage: -40…85 °C

Ambient air temperature for operation: 0…50 °C mounting side by side; 0…60 °C 2 cm spacing

Pollution degree: 2 conforming to IEC 60664-1

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 2.7 cm

Package 1 Width: 8.2 cm

Package 1 Length: 8.5 cm

Package 1 Weight: 101.0 g

Unit Type of Package 2: S02

Number of Units in Package 2: 47

Package 2 Height: 15.0 cm

Package 2 Width: 30.0 cm

Package 2 Length: 40.0 cm

Package 2 Weight: 5.253 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free: Yes

China RoHS Regulation: X

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP1607005EN

Circularity Profile: ENVEOLI1607005EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins