Schneider-Electric
LRD163
Tariff code: 8536490099
Link to the manufacturers site: LRD163 - TeSys LRD thermal overload relays - 9...13 A - class 10A
Main
Range: TeSys; TeSys Deca
Product name: TeSys LRD; TeSys Deca
Product or component type: Differential thermal overload relay
Device short name: LRD
Relay application: Motor protection
Product compatibility: LC1D18; LC1D12; LC1D32; LC1D25; LC1D38
Network type: DC; AC
Thermal overload class: Class 10A conforming to IEC 60947-4-1
Thermal protection adjustment range: 9…13 A
[Ui] rated insulation voltage: Power circuit: 600 V conforming to CSA; Power circuit: 600 V conforming to UL; Power circuit: 690 V conforming to IEC 60947-4-1
Complementary
Network frequency: 0...400 Hz
Mounting support: Plate, with specific accessories; Rail, with specific accessories; Under contactor
Tripping threshold: 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Auxiliary contact composition: 1 NO + 1 NC
[Ith] conventional free air thermal current: 5 A for signalling circuit
Permissible current: 3 A at 120 V AC-15 for signalling circuit; 0.22 A at 125 V DC-13 for signalling circuit
[Ue] rated operational voltage: 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated fuse rating: 4 A gG for signalling circuit; 4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage: 6 kV
Phase failure sensitivity: Tripping current 130 % of Ir on two phase, the last one at 0
Control type: Red push-button: stop; Blue push-button: reset
Temperature compensation: -20…60 °C
Connections - terminals: Control circuit: spring terminals 1 cable(s) 1…2.5 mm² solid without cable end; Control circuit: spring terminals 1 cable(s) 1…2.5 mm² flexible without cable end; Power circuit: spring terminals 1 cable(s) 1.5…4 mm² flexible without cable end; Power circuit: spring terminals 1 cable(s) 1.5…4 mm² flexible with cable end
height: 93 mm
Width: 45 mm
Depth: 72 mm
Net weight: 0.14 kg
Compatibility code: LRD
Environment
Climatic withstand: conforming to IACS E10
IP degree of protection: IP20 conforming to IEC 60529
Ambient air temperature for operation: -20…60 °C without derating conforming to IEC 60947-4-1
Ambient air temperature for storage: -60…70 °C
Flame retardance: V1 conforming to UL 94
Mechanical robustness: Vibrations: 6 Gn conforming to IEC 60068-2-6; Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
Dielectric strength: 1.89 kV at 50 Hz conforming to IEC 60947-1
Standards: EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; GB/T 14048.4; GB/T 14048.5; EN 50495
product certifications: IEC; UL; CSA; CCC; EAC; BV; RINA; DNV-GL; LROS (Lloyds register of shipping); ATEX INERIS; UKCA
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 5.5 cm
Package 1 Width: 8.0 cm
Package 1 Length: 10.0 cm
Package 1 Weight: 192.0 g
Unit Type of Package 2: S02
Number of Units in Package 2: 23
Package 2 Height: 15.0 cm
Package 2 Width: 30.0 cm
Package 2 Length: 40.0 cm
Package 2 Weight: 4.66 kg
Offer Sustainability
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Compliant with Exemptions
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure: ENVPEP080405EN
Circularity Profile: ENVEOLI0804005_V1
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins