Schneider-Electric
LC7K09008M7
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: LC7K09008M7 - TeSys K contactor - 4P (2 NO + 2 NC) - AC-1 <= 440 V 20 A - 220...230 V AC coil
Main
range of product: TeSys K
range: TeSys
product or component type: Contactor
product name: TeSys K
device short name: LC7K
device application: Control
contactor application: Resistive load
Complementary
utilisation category: AC-1
poles description: 4P
pole contact composition: 2 NO + 2 NC
[Ue] rated operational voltage: Power circuit: 690 V AC 50/60 Hz
[Ie] rated operational current: 20 A (at <50 °C) at <= 440 V AC AC-1 for power circuit; 16 A (at <70 °C) at 690 V AC AC-1 for power circuit
control circuit type: AC at 50/60 Hz silent
[Uc] control circuit voltage: 220...230 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 8 kV
overvoltage category: III
[Ith] conventional free air thermal current: 20 A (at 50 °C) for power circuit
Irms rated making capacity: 110 A AC for power circuit conforming to NF C 63-110; 110 A AC for power circuit conforming to IEC 60947
rated breaking capacity: 110 A at 415 V conforming to IEC 60947; 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 110 A at 220...230 V conforming to IEC 60947; 110 A at 380...400 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand current: 90 A 50 °C - 1 s for power circuit; 85 A 50 °C - 5 s for power circuit; 80 A 50 °C - 10 s for power circuit; 60 A 50 °C - 30 s for power circuit; 45 A 50 °C - 1 min for power circuit; 40 A 50 °C - 3 min for power circuit; 20 A 50 °C - >= 15 min for power circuit
associated fuse rating: 25 A gG at <= 440 V for power circuit; 25 A aM for power circuit
average impedance: 3 mOhm - Ith 20 A 50 Hz for power circuit
[Ui] rated insulation voltage: Power circuit: 600 V conforming to UL 508; Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V conforming to CSA C22.2 No 14
inrush power in VA: 3 VA (at 20 °C)
hold-in power consumption in VA: 3 VA (at 20 °C)
heat dissipation: 3 W
control circuit voltage limits: Operational: 0.85...1.1 Uc (at <50 °C); Drop-out: 0.1...0.75 Uc (at <50 °C)
connections - terminals: Screw clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end
maximum operating rate: 3600 cyc/h
signalling circuit frequency: <= 400 Hz
mounting support: Plate; Rail
tightening torque: 1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2; 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
operating time: 30...40 ms coil energisation and NO closing; 25...35 ms coil energisation and NC opening; 30 ms coil de-energisation and NO opening; 40 ms coil de-energisation and NC closing
safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability: 10 Mcycles
electrical durability: 0.18 Mcycles 20 A AC-1 at Ue <= 440 V
mechanical robustness: Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27; Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
height: 58 mm
width: 45 mm
depth: 57 mm
net weight: 0.225 kg
compatibility code: LC7K
Environment
standards: BS 5424; IEC 60947; NF C 63-110; VDE 0660
product certifications: CSA; UL
IP degree of protection: IP2x conforming to VDE 0106
protective treatment: TC conforming to IEC 60068; TC conforming to DIN 50016
ambient air temperature for storage: -50…80 °C
operating altitude: 2000 m without derating
flame retardance: V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102
Offer Sustainability
EU RoHS Directive: Compliant
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.