Schneider-Electric
LC3F225M7A64
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: LC3F225M7A64 - TeSys F - star delta starter - 3 x 3P (3 NO) - 225 A - 220/230 V AC coil
Main
range of product: TeSys F
range: TeSys
product name: TeSys F
product or component type: Star delta starter
device short name: LC3F
contactor application: Motor control
utilisation category: AC-3
device presentation: Pre-wired
poles description: 3 x 3P
pole contact composition: 3 x 3 NO
[Ue] rated operational voltage: Power circuit: <= 1000 V AC 16 Hz 2/3...200 Hz
[Ie] rated operational current: 225 A (at <55 °C) at <= 440 V AC AC-3 for power circuit
motor power kW: 100 kW at 220/230 V AC 50/60 Hz; 200 kW at 380/400 V AC 50/60 Hz; 200 kW at 415 V AC 50/60 Hz; 220 kW at 440 V AC 50/60 Hz
control circuit type: AC at 50/60 Hz
[Uc] control circuit voltage: 220/230 V AC 50/60 Hz
auxiliary contact composition: 1 NC for KM1 star contactor; 1 NO for KM1 star contactor; 2 NC for KM2 line contactor; 1 NO for KM2 line contactor; 1 NC for KM3 delta contactor; 2 NO for KM3 delta contactor
[Uimp] rated impulse withstand voltage: 8 kV
[Ui] rated insulation voltage: 1000 V conforming to IEC 60947-4-1; 1500 V conforming to VDE 0110 group C
interlocking type: Mechanical
mounting support: Plate
standards: EN 60947-1; EN 60947-4-1; IEC 60947-1; IEC 60947-4-1; JIS C8201-4-1
product certifications: CCC; RINA; UL; ABS; CSA; CB; RMRoS; LROS (Lloyds register of shipping); DNV
Complementary
[Ith] conventional free air thermal current: 315 A 40 °C
Irms rated making capacity: 2250 A conforming to IEC 60947-4-1
rated breaking capacity: 1800 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current: 1800 A 40 °C - 10 s; 1000 A 40 °C - 30 s; 850 A 40 °C - 1 min; 560 A 40 °C - 3 min; 440 A 40 °C - 10 min
associated fuse rating: 315 A gG at <= 440 V; 250 A aM at <= 440 V
connections - terminals: Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end; Power circuit: bar 2 - busbar cross section: 32 x 4 mm; Power circuit: bolted connection; Power circuit: lugs-ring terminals 1 185 mm²; Power circuit: connector 1 185 mm²
bolt diameter: M10
tightening torque: Control circuit: 1.2 N.m; Power circuit: 35 N.m
operating time: 20...35 ms closing; 7...15 ms opening
mechanical durability: 10 Mcycles
maximum operating rate: 2400 cyc/h 55 °C
starting time: 30 s
control circuit voltage limits: Operational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C); Drop-out: 0.35...0.55 Uc at 50/60 Hz (at <55 °C)
inrush power in VA: 805 VA 50 Hz cos phi 0.3 (at 20 °C); 970 VA 60 Hz cos phi 0.3 (at 20 °C)
hold-in power consumption in VA: 55 VA 50 Hz cos phi 0.3 (at 20 °C); 66 VA 60 Hz cos phi 0.3 (at 20 °C)
heat dissipation: 18…24 W
width: 525 mm
height: 110 mm
depth: 235 mm
net weight: 16.625 kg
power range: 55…100 kW at 200…240 V 3 phases; 110…220 kW at 380…440 V 3 phases
motor starter type: Star delta starter
contactor coil voltage: 220 V AC standard; 230 V AC standard
Environment
IP degree of protection: IP20 front face with shrouds conforming to IEC 60529; IP20 front face with shrouds conforming to VDE 0106
protective treatment: TH
ambient air temperature for storage: -60…80 °C
ambient air temperature for operation: -5…55 °C; -40…70 °C at Uc
operating altitude: 3000 m without derating
mechanical robustness: Vibrations contactor open: 2 Gn, 5...300 Hz; Shocks contactor closed: 15 Gn for 11 ms; Vibrations contactor closed: 5 Gn, 5...300 Hz; Shocks contactor open: 7 Gn for 11 ms
Offer Sustainability
Sustainable offer status: Green Premium product
EU RoHS Directive: Compliant
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure: ENVPEP080208EN
Circularity Profile: ENVEOLI100418EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
PVC free: Yes
© 2018 Alplan Kft.