Skip to main content

Schneider-Electric
LC1F800

Mágneskapcsoló, AC3, 800A, tekercs nélkül
In stock: 1 pc(s)
Barcode: 3389110747072
Tariff code: 8536490099

This product is discontinued.

This product is no longer manufactured, but we have it in stock. Please contact us for price and delivery information!

Link to the manufacturers site: LC1F800 - Mágneskapcsoló, AC3, 800A, tekercs nélkül

Main

range of product: TeSys F

range: TeSys

product name: TeSys F

product or component type: Contactor

device short name: LC1F

contactor application: Motor control; Resistive load

utilisation category: AC-3; AC-1; AC-4

poles description: 3P

pole contact composition: 3 NO

[Ue] rated operational voltage: <= 1000 V AC 50/60 Hz; <= 460 V DC

[Ie] rated operational current: 1000 A (at <40 °C) at <= 440 V AC AC-1; 800 A (at <55 °C) at <= 440 V AC AC-3

motor power kW: 450 kW at 1000 V AC 50/60 Hz (AC-3); 450 kW at 500 V AC 50/60 Hz (AC-3); 475 kW at 660...690 V AC 50/60 Hz (AC-3); 110 kW at 400 V AC 50/60 Hz (AC-4); 450 kW at 380...400 V AC 50/60 Hz (AC-3); 450 kW at 415 V AC 50/60 Hz (AC-3); 450 kW at 440 V AC 50/60 Hz (AC-3); 250 kW at 220...240 V AC 50/60 Hz (AC-3)

Complementary

[Uc] control circuit voltage: 110...400 V AC 40...400 Hz with LX1/LX9 coil; 110...400 V DC with LX4 coil; 100...250 V AC 50/60 Hz with LXE coil; 100...380 V DC with LXE coil

[Uimp] rated impulse withstand voltage: 8 kV

overvoltage category: III

[Ith] conventional free air thermal current: 1000 A (at 40 °C)

Irms rated making capacity: 8000 A AC conforming to IEC 60947-4-1

rated breaking capacity: 6400 A conforming to IEC 60947-4-1

[Icw] rated short-time withstand current: 2600 A 40 °C - 3 min; 5500 A 40 °C - 10 s; 4600 A 40 °C - 30 s; 3600 A 40 °C - 1 min; 1700 A 40 °C - 10 min

associated fuse rating: 1000 A gG at <= 440 V; 800 A aM at <= 440 V

average impedance: 0.12 mOhm - Ith 1000 A 50 Hz

[Ui] rated insulation voltage: 1000 V conforming to IEC 60947-4-1; 1500 V conforming to VDE 0110 group C

control circuit voltage limits: Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil; Drop-out: 0.3...0.5 Uc AC 40...400 Hz with LX1/LX9 coil; Operational: 0.85...1.1 Uc DC with LX4 coil; Drop-out: 0.3...0.5 Uc DC with LX4 coil; Operational: 85...275 V AC 50/60 Hz with LXE coil; Drop-out: 0...60 V AC 50/60 Hz with LXE coil; Operational: 85...418 V DC with LXE coil; Drop-out: 0...45 V DC with LXE coil

power dissipation per pole: 120 W AC-1; 77 W AC-3

heat dissipation: 25 W; 2.2…5.5 W

operating time: 60...80 ms closing for with LX1/LX9 coil; 160...180 ms opening for with LX1/LX9 coil; 60...80 ms closing for with LX4 coil; 40...50 ms opening for with LX4 coil; 40...80 ms closing for with LXE coil; 6...54 ms opening for with LXE coil

mounting support: Plate

standards: IEC 60947-1; JIS C8201-4-1; EN 60947-1; IEC 60947-4-1; EN 60947-4-1

product certifications: CB; CSA; LROS (Lloyds register of shipping); ABS; CCC; UL; UKCA

connections - terminals: Power circuit: bar 2 cable(s) - busbar cross section: 60 x 5 mm; Power circuit: bolted connection; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²; Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²

tightening torque: Power circuit: 58 N.m; Control circuit: 1.2 N.m

mechanical durability: 5 Mcycles

inrush power in VA: 1700 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil; 1900 VA (at 20 °C)with LX4 coil; 460…730 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil; 500…680 VA cos phi 0.5 (at 20 °C)with LXE coil

hold-in power consumption in VA: 12 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil; 12 VA (at 20 °C)with LX4 coil; 7…10 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil; 4.0…5.5 VA cos phi 0.5 (at 20 °C)with LXE coil

maximum operating rate: 600 cyc/h 55 °C

compatibility code: LC1F

Environment

IP degree of protection: IP20 front face with shrouds conforming to IEC 60529; IP20 front face with shrouds conforming to VDE 0106

protective treatment: TH

ambient air temperature for operation: -5…55 °C

ambient air temperature for storage: -60…80 °C

permissible ambient air temperature around the device: -5…55 °C

operating altitude: 3000 m without derating

mechanical robustness: Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 4 Gn, 5...300 Hz; Shocks contactor open: 6 Gn for 1/2 sine wave (11 ms); Shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms)

height: 304 mm

width: 309 mm

depth: 255 mm

net weight: 18.75 kg

Packing Units

Number of Units in Package 1: 1

Number of Units in Package 2: 4

Package 1 Height: 33.5 cm

Package 1 Length: 44.5 cm

Package 1 Weight: 17.195 kg

Package 1 Width: 33.5 cm

Package 2 Height: 75 cm

Package 2 Length: 80 cm

Package 2 Weight: 77.28 kg

Package 2 Width: 60 cm

Unit Type of Package 1: PCE

Unit Type of Package 2: P06

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Compliant

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure: ENVPEP1505009EN

Circularity Profile: ENVEOLI1505009EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

© 2018 Alplan Kft.