Skip to main content

Schneider-Electric
LC1E250F5

EasyPact TVS contactor 3P(3 NO) - AC-3 - <= 440 V 250A - 110 V AC coil
Barcode: 3606480323904
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: LC1E250F5 - EasyPact TVS contactor 3P(3 NO) - AC-3 - <= 440 V 250A - 110 V AC coil

Main

range: EasyPact

product name: EasyPact TVS

product or component type: Contactor

device short name: LC1E

contactor application: Motor control; Resistive load

utilisation category: AC-1; AC-3

poles description: 3P

pole contact composition: 3 NO

[Ue] rated operational voltage: Power circuit: <= 690 V AC 50/60 Hz

[Ie] rated operational current: 250 A (at <55 °C) at <= 440 V AC AC-3 for power circuit; 300 A (at <40 °C) at <= 440 V AC AC-1 for power circuit

motor power kW: 75 kW at 220...230 V AC 50/60 Hz; 132 kW at 380...400 V; 140 kW at 415 V; 140 kW at 440 V; 160 kW at 500 V; 160 kW at 660...690 V

control circuit type: AC at 50 Hz

[Uc] control circuit voltage: 110 V AC 50 Hz

height: 197 mm

width: 168.5 mm

depth: 181 mm

net weight: 4.7 kg

Complementary

[Uimp] rated impulse withstand voltage: 8 kV coil not connected to the power circuit conforming to IEC 60947

[Ui] rated insulation voltage: 690 V conforming to IEC 60947-4-1

overvoltage category: III

[Ith] conventional free air thermal current: 36 A (at 55 °C)

Irms rated making capacity: 2500 A at 440 V AC for power circuit conforming to IEC 60947-4-1

rated breaking capacity: 2000 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current: 1800 A 40 °C - 10 s for power circuit

associated fuse rating: 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1; 315 A gG at <= 690 V coordination type 1 for power circuit

average impedance: 0.32 mOhm - Ith 300 A 50 Hz for power circuit

power dissipation per pole: 20 W AC-3; 29 W AC-1

control circuit voltage limits: Operational: 0.85...1.1 Uc at 50 Hz (at <55 °C); Drop-out: 0.35...0.55 Uc at 50 Hz (at <55 °C)

operating time: 20...35 ms on closing; 7...15 ms on opening

mechanical durability: 500000 cycles

maximum operating rate: 1200 cyc/h 55 °C

inrush power in VA: 805 VA 50 Hz cos phi 0.3 (at 20 °C); 970 VA 60 Hz cos phi 0.3 (at 20 °C)

hold-in power consumption in VA: 55 VA 50 Hz cos phi 0.3 (at 20 °C); 66 VA 60 Hz cos phi 0.3 (at 20 °C)

heat dissipation: 18…24 W for control circuit

minimum switching current: 5 mA for control circuit

minimum switching voltage: 17 V for control circuit

non-overlap time: 1.5 ms on energisation guaranteed between NC and NO contact; 1.5 ms on de-energisation guaranteed between NC and NO contact

insulation resistance: > 10 MOhm for control circuit

electrical durability: 200000 cycles AC-1; 700000 cycles AC-3

mounting support: Plate

connections - terminals: Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end; Power circuit: cable with lug - external diameter: 185 mm; Power circuit: bars 2 - busbar cross section: 32 x 4 mm

tightening torque: Control circuit: 1.2 N.m; Power circuit: 35 N.m

Environment

standards: IEC 60947-1; IEC 60947-4-1; IEC 60947-5-1

product certifications: EAC; CE

IP degree of protection: IP00 conforming to IEC 60529

pollution degree: 3

ambient air temperature for operation: -5…55 °C

ambient air temperature for storage: -60…80 °C

permissible ambient air temperature around the device: -20…70 °C at Uc

operating altitude: 3000 m without derating

fire resistance: 850 °C conforming to IEC 60695-2-1

mechanical robustness: Vibrations contactor open: 1.5 Gn, 5...300 Hz; Vibrations contactor closed: 3 Gn, 5...300 Hz; Shocks contactor open: 6 Gn for 11 ms; Shocks contactor closed: 7 Gn for 11 ms

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Compliant

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure: ENVPEP1406035EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

© 2018 Alplan Kft.