Skip to main content

Schneider-Electric
LC1E120E5

EasyPact TVS contactor 3P(3 NO) - AC-3 - <= 440 V 120A - 48 V AC coil
Barcode: 3606480323652
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: LC1E120E5 - EasyPact TVS contactor 3P(3 NO) - AC-3 - <= 440 V 120A - 48 V AC coil

Main

range: EasyPact

product name: EasyPact TVS

product or component type: Contactor

device short name: LC1E

contactor application: Motor control; Resistive load

utilisation category: AC-1; AC-3

poles description: 3P

pole contact composition: 3 NO

[Ue] rated operational voltage: Power circuit: <= 690 V AC 50/60 Hz

[Ie] rated operational current: 120 A (at <55 °C) at <= 440 V AC AC-3 for power circuit; 150 A (at <55 °C) at <= 440 V AC AC-1 for power circuit

motor power kW: 37 kW at 220...230 V AC 50/60 Hz (AC-3); 55 kW at 380...400 V AC 50/60 Hz (AC-3); 59 kW at 415 V AC 50/60 Hz (AC-3); 59 kW at 440 V AC 50/60 Hz (AC-3); 75 kW at 500 V AC 50/60 Hz (AC-3); 80 kW at 660...690 V AC 50/60 Hz (AC-3)

control circuit type: AC at 50 Hz

[Uc] control circuit voltage: 48 V AC 50 Hz

height: 158 mm

width: 120 mm

depth: 132 mm

net weight: 2.3 kg

Complementary

auxiliary contact composition: 1 NO + 1 NC

[Uimp] rated impulse withstand voltage: 8 kV coil not connected to the power circuit conforming to IEC 60947

[Ui] rated insulation voltage: 690 V conforming to IEC 60947-4-1

overvoltage category: III

[Ith] conventional free air thermal current: 25 A (at 55 °C) for power circuit

Irms rated making capacity: 1200 A at 440 V AC for power circuit conforming to IEC 60947-4-1

rated breaking capacity: 960 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current: 1100 A 40 °C - 10 s for power circuit

associated fuse rating: 250 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1; 10 A gG at <= 690 V coordination type 1 for power circuit

average impedance: 0.6 mOhm - Ith 150 A 50 Hz for power circuit

power dissipation per pole: 8.6 W AC-3; 14 W AC-1

control circuit voltage limits: Operational: 0.85...1.1 Uc at 50 Hz (at <55 °C); Drop-out: 0.35...0.55 Uc at 50 Hz (at <55 °C)

operating time: 20...50 ms on closing; 6...20 ms on opening

mechanical durability: 400000 cycles

maximum operating rate: 1200 cyc/h 55 °C

inrush power in VA: 300 VA 50 Hz cos phi 0.8 (at 20 °C); 300 VA 60 Hz cos phi 0.8 (at 20 °C)

hold-in power consumption in VA: 22 VA 50 Hz cos phi 0.3 (at 20 °C); 22 VA 60 Hz cos phi 0.3 (at 20 °C)

heat dissipation: 3…8 W for control circuit

minimum switching current: 5 mA for control circuit

minimum switching voltage: 17 V for control circuit

non-overlap time: 1.5 ms on energisation guaranteed between NC and NO contact; 1.5 ms on de-energisation guaranteed between NC and NO contact

insulation resistance: > 10 MOhm for control circuit

electrical durability: 800000 cycles AC-3; 250000 cycles AC-1

mounting support: DIN rail; Plate

connections - terminals: Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 1 10…120 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 2 20…170 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 1 10…120 mm² - cable stiffness: solid without cable end; Power circuit: screw clamp terminals 2 20…170 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: solid without cable end

tightening torque: Power circuit: 12 N.m; Control circuit: 1.2 N.m

Environment

standards: IEC 60947-1; IEC 60947-4-1; IEC 60947-5-1

product certifications: CE; EAC

IP degree of protection: IP2x conforming to IEC 60529

protective treatment: TH (pollution degree 3) conforming to IEC 60068-2-30

pollution degree: 3

ambient air temperature for operation: -5…55 °C

ambient air temperature for storage: -60…80 °C

permissible ambient air temperature around the device: -20…70 °C at Uc

operating altitude: 3000 m without derating

fire resistance: 850 °C conforming to IEC 60695-2-1

mechanical robustness: Vibrations contactor open: 1.5 Gn, 5...300 Hz; Vibrations contactor closed: 3 Gn, 5...300 Hz; Shocks contactor open: 6 Gn for 11 ms; Shocks contactor closed: 7 Gn for 11 ms

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation: X

Environmental Disclosure: ENVPEP1405005EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

© 2018 Alplan Kft.