Skip to main content

Schneider-Electric
LC1D80E5

TeSys D contactor 3P 80A AC-3 <= 440V - aux 1NO+1NC - coil 48V 50Hz
Net discounted price 188.01 EUR
Available when ordered (delivery time: 6 working day(s))
Barcode: 3389110440423
Tariff code: 8536419089

Link to the manufacturers site: LC1D80E5 - TeSys D contactor 3P 80A AC-3 <= 440V - aux 1NO+1NC - coil 48V 50Hz

Main

Range: TeSys

Range of produc: TeSys Deca

Product or component type: Contactor

Device short name: LC1D

contactor application: Motor control; Resistive load

utilisation category: AC-3; AC-3e; AC-4; AC-1

Poles description: 3P

[Ue] rated operational voltage: Power circuit: <= 690 V AC 25...400 Hz; Power circuit: <= 300 V DC

[Ie] rated operational current: 80 A (at <60 °C) at <= 440 V AC-3 for power circuit; 125 A (at <60 °C) at <= 440 V AC-1 for power circuit; 80 A (at <60 °C) at <= 440 V AC-3e for power circuit

[Uc] control circuit voltage: 48 V AC 50 Hz

Complementary

Motor power kW: 22 kW at 220...230 V AC 50 Hz (AC-3); 37 kW at 380...400 V AC 50 Hz (AC-3); 45 kW at 415...440 V AC 50 Hz (AC-3); 55 kW at 500 V AC 50 Hz (AC-3); 45 kW at 660...690 V AC 50 Hz (AC-3); 15 kW at 400 V AC 50 Hz (AC-4); 22 kW at 220...230 V AC 50 Hz (AC-3e); 37 kW at 380...400 V AC 50 Hz (AC-3e); 45 kW at 415...440 V AC 50 Hz (AC-3e); 55 kW at 500 V AC 50 Hz (AC-3e); 45 kW at 660...690 V AC 50 Hz (AC-3e)

Motor power hp: 7.5 hp at 120 V AC 50/60 Hz for 1 phase motors; 15 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 30 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 30 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 60 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 60 hp at 575/600 V AC 50/60 Hz for 3 phases motors

Compatibility code: LC1D

Pole contact composition: 3 NO

Contact compatibility: M12

Protective cover: With

[Ith] conventional free air thermal current: 10 A (at 60 °C) for signalling circuit; 125 A (at 60 °C) for power circuit

Irms rated making capacity: 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 1100 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity: 1100 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current: 135 A 40 °C - 10 min for power circuit; 320 A 40 °C - 1 min for power circuit; 640 A 40 °C - 10 s for power circuit; 990 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit

Associated fuse rating: 10 A gG for signalling circuit conforming to IEC 60947-5-1; 200 A gG at <= 690 V coordination type 1 for power circuit; 160 A gG at <= 690 V coordination type 2 for power circuit

Average impedance: 0.8 mOhm - Ith 125 A 50 Hz for power circuit

Power dissipation per pole: 5.1 W AC-3; 12.5 W AC-1; 5.1 W AC-3e

[Ui] rated insulation voltage: Power circuit: 1000 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified

Overvoltage category: III

Pollution degree: 3

[Uimp] rated impulse withstand voltage: 8 kV conforming to IEC 60947

Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability: 10 Mcycles

Electrical durability: 1.5 Mcycles 80 A AC-3 at Ue <= 440 V; 0.8 Mcycles 125 A AC-1 at Ue <= 440 V; 1.5 Mcycles 80 A AC-3e at Ue <= 440 V

Control circuit type: AC at 50 Hz

Coil technology: Without built-in suppressor module

Control circuit voltage limits: 0.3...0.6 Uc (-40…70 °C):drop-out AC 50 Hz; 0.85...1.1 Uc (-40…55 °C):operational AC 50 Hz; 1...1.1 Uc (55…70 °C):operational AC 50 Hz

Inrush power in VA: 200 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in VA: 20 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation: 6…10 W at 50 Hz

Operating time: 20...35 ms closing; 6...20 ms opening

Maximum operating rate: 3600 cyc/h 60 °C

Connections - terminals: Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end; Power circuit: connector 1 4…50 mm² - cable stiffness: flexible without cable end; Power circuit: connector 2 4…25 mm² - cable stiffness: flexible without cable end; Power circuit: connector 1 4…50 mm² - cable stiffness: flexible with cable end; Power circuit: connector 2 4…16 mm² - cable stiffness: flexible with cable end; Power circuit: connector 1 4…50 mm² - cable stiffness: solid without cable end; Power circuit: connector 2 4…25 mm² - cable stiffness: solid without cable end

Tightening torque: Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm; Power circuit: 12 N.m - on connector hexagonal screw head 4 mm; Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

Auxiliary contact composition: 1 NO + 1 NC

Auxiliary contacts type: type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1

Signalling circuit frequency: 25...400 Hz

Minimum switching voltage: 17 V for signalling circuit

Minimum switching current: 5 mA for signalling circuit

Insulation resistance: > 10 MOhm for signalling circuit

Non-overlap time: 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact

mounting support: Plate; Rail

Environment

Standards: EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; CSA C22.2 No 60947-4-1

product certifications: UL; CSA; CCC; EAC; LROS (Lloyds register of shipping); DNV-GL; RINA; BV

IP degree of protection: IP20 front face conforming to IEC 60529

Protective treatment: TH conforming to IEC 60068-2-30

Climatic withstand: conforming to IACS E10 exposure to damp heat

Permissible ambient air temperature around the device: -40…60 °C; 60…70 °C with derating

Operating altitude: 0...3000 m

Fire resistance: 850 °C conforming to IEC 60695-2-1

Flame retardance: V1 conforming to UL 94

Mechanical robustness: Vibrations contactor open (2 Gn, 5...300 Hz) ; Shocks contactor open (8 Gn for 11 ms) ; Vibrations contactor closed (3 Gn, 5...300 Hz) ; Shocks contactor closed (10 Gn for 11 ms)

height: 127 mm

Width: 85 mm

Depth: 130 mm

Net weight: 1.59 kg

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 15.5 cm

Package 1 Width: 13.5 cm

Package 1 Length: 9.5 cm

Package 1 Weight: 1.564 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

China RoHS Regulation:  Pro-active China RoHS declaration (out of China RoHS legal scope)

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP110205EN

Circularity Profile: N/A

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

PVC free: Yes