Skip to main content

Schneider-Electric
ATV71EXC2C13N4

enclosed variable speed drive ATV71 Plus - 132 kW - 400 V - IP23
Barcode: 3389118320024
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: ATV71EXC2C13N4 - enclosed variable speed drive ATV71 Plus - 132 kW - 400 V - IP23

Main

range of product: Altivar 71 Plus

product or component type: Variable speed drive

device short name: ATV71 Plus

product destination: Synchronous motors; Asynchronous motors

product specific application: Complex, high-power machines

assembly style: In floor-standing enclosure compact version

kit composition: An IP65 remote mounting kit for graphic display terminal; A wired ready-assembled Sarel Spacial 6000 enclosure; ATV71HC13N4D drive on heatsink; Terminals/bars for motor connection; A switch and fast-acting semi-conductor fuses; A line choke

EMC filter: Integrated

network number of phases: 3 phases

[Us] rated supply voltage: 380...415 V +/- 10 %

supply voltage limits: 342…457 V

supply frequency: 50...60 Hz +/- 5 %

network frequency: 47.5...63 Hz

motor power kW: 132 kW at 380...415 V

line current: 229 A for 400 V / 132 kW

Complementary

apparent power: 157 kVA for 400 V / 132 kW

prospective line Isc: 100 kA with external fuses

continuous output current: 259 A at 2.5 kHz, 400 V / 132 kW

maximum transient current: 389 A for 60 s / 132 kW

speed drive output frequency: 0…500 Hz

nominal switching frequency: 2.5 kHz

switching frequency: 2.5...8 kHz with derating factor; 2...8 kHz adjustable

speed range: 1…100 in open-loop mode, without speed feedback

speed accuracy: +/- 0.01 % of nominal speed in closed-loop mode with encoder feedback 0.2 Tn to Tn; +/- 10 % of nominal slip without speed feedback 0.2 Tn to Tn

torque accuracy: +/- 15 % in open-loop mode, without speed feedback; +/- 5 % in closed-loop mode with encoder feedback

transient overtorque: 170 % of nominal motor torque +/- 10 % for 60 s; 220 % of nominal motor torque +/- 10 % for 2 s

braking torque: <= 150 % with braking or hoist resistor; 30 % without braking resistor

asynchronous motor control profile: Voltage/frequency ratio - Energy Saving, quadratic U/f; Voltage/frequency ratio, 2 points; Flux vector control without sensor, 2 points; Flux vector control without sensor, ENA (energy Adaptation) system; Flux vector control without sensor, standard; Voltage/frequency ratio, 5 points; Flux vector control with sensor, standard

synchronous motor control profile: Vector control without sensor, standard; Vector control with sensor, standard

regulation loop: Adjustable PI regulator

motor slip compensation: Suppressable; Adjustable; Not available in voltage/frequency ratio (2 or 5 points); Automatic whatever the load

overvoltage category: Class 3 conforming to EN 50178

local signalling: LCD display unit for operation function, status and configuration - mounted in the front door

output voltage: <= power supply voltage

isolation: Electrical between power and control

type of cable: IEC cable at 40 °C, copper 70 °C / PVC

electrical connection: Terminal - 2.5 mm² / AWG 14 (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR) entry from the bottom; Terminal M10 - 2 x 150 mm² (L1/R, L2/S, L3/T) entry from the bottom; Terminal M12 - 2 x 240 mm² (U/T1, V/T2, W/T3) entry from the bottom

motor recommanded cable cross section: 3 x 150 mm²

short-circuit protection: 400 A fuse protection type gI - power supply upstream

supply: External supply: 24 V DC (19…30 V), <1 A; Internal supply for reference potentiometer: 10 V DC (10…11 V), <10 mA; Internal supply: 24 V DC (21…27 V), <100 mA

analogue input number: 2

analogue input type: AI2 software-configurable voltage: 0...10 V DC, 24 V max, impedance: 30000 Ohm, sampling time: 1.5…2.5 ms, resolution: 11 bits; AI1-/Al1+ bipolar differential voltage: +/- 10 V DC, 24 V max, sampling time: 1.5…2.5 ms, resolution: 11 bits + sign; AI2 software-configurable current: 0...20 mA/4...20 mA, impedance: 250 Ohm, sampling time: 1.5…2.5 ms, resolution: 11 bits

analogue output number: 1

analogue output type: Software-configurable voltage: (AO1) 0...10 V DC - 470 Ohm - sampling time: 1.5…2.5 ms - resolution: 10 bits; Software-configurable current: (AO1) 0...20 mA/4...20 mA - 500 Ohm - sampling time: 1.5…2.5 ms - resolution: 10 bits

discrete output number: 2

discrete output type: Configurable relay logic: (R1A, R1B, R1C)NO/NC - 6.5...7.5 ms - 100000 cycles; Configurable relay logic: (R2A, R2B)NO - 6.5...7.5 ms - 100000 cycles

minimum switching current: 3 mA at 24 V DC (configurable relay logic)

maximum switching current: 5 A at 250 V AC on resistive load - cos phi = 1 (R1, R2); 5 A at 30 V DC on resistive load - L/R = 0 ms (R1, R2); 2 A at 250 V AC on inductive load - cos phi = 0.4 (R1, R2); 2 A at 30 V DC on inductive load - L/R = 7 ms (R1, R2)

discrete input number: 7

discrete input type: Programmable (LI1...LI5) at 24 V DC <= 30 V level 1 PLC 3.5 kOhm (duration=1.5…2.5 ms); Switch-configurable (LI6) at 24 V DC <= 30 V level 1 PLC 1.5 kOhm (duration=1.5…2.5 ms); Safety input (PWR) at 24 V DC <= 30 V 1.5 kOhm

discrete input logic: Positive logic (source) (LI1...LI6), 0...5 V (state 0), 11...30 V (state 1); Negative logic (sink) (LI1...LI6), 16...30 V (state 0), 0...10 V (state 1); Positive logic (source) (PWR), 0...2 V (state 0), 17...30 V (state 1)

acceleration and deceleration ramps: Linear adjustable separately from 0.01 to 9000 s; S, U or customized; Automatic adaptation of ramp if braking capacity exceeded, by using resistor

braking to standstill: By DC injection

protection type: Against exceeding limit speed: drive; Against input phase loss: drive; Break on the control circuit: drive; Input phase breaks: drive; Line supply overvoltage: drive; Line supply undervoltage: drive; Overcurrent between output phases and earth: drive; Overheating protection: drive; Overvoltages on the DC bus: drive; Short-circuit between motor phases: drive; Thermal protection: drive; Input phase breaks: motor; Power removal: motor; Thermal protection: motor

dielectric strength: 3535 V DC between earth and power terminals; 5092 V DC between control and power terminals

insulation resistance: > 1 mOhm 500 V DC for 1 minute to earth

frequency resolution: Analog input: 0.024/50 Hz; Display unit: 0.1 Hz

communication port protocol: Modbus; CANopen

connector type: 1 RJ45 (on front face) for Modbus; 1 RJ45 (on terminal) for Modbus; Male SUB-D 9 on RJ45 for CANopen

physical interface: 2-wire RS 485 for Modbus

transmission frame: RTU for Modbus

transmission rate: 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal; 9600 bps, 19200 bps for Modbus on front face; 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen

data format: 8 bits, 1 stop, even parity for Modbus on front face; 8 bits, odd even or no configurable parity for Modbus on terminal

type of polarization: No impedance for Modbus

number of addresses: 1…127 for CANopen; 1…247 for Modbus

method of access: Slave CANopen

option card: Communication card for CC-Link; Communication card for DeviceNet; Communication card for EtherNet/IP; Communication card for Fipio; Communication card for Interbus-S; Communication card for Modbus Plus; Communication card for Modbus/Uni-Telway; Communication card for Profibus DP; Communication card for Profibus DP V1; Communication card for Modbus TCP/IP; Controller inside programmable card; Basic I/O extension card; Extended I/O extension card; Encoder interface cards

function available: Safe standstill for power circuit; PTC relay for power circuit; Pt100 relay for power circuit; Insulation monitoring for power circuit; Design for IT networks for power circuit; External 230 V supply terminals for power circuit; Buffer voltage 24 V DC power supply for power circuit; External 24 V DC supply terminals for power circuit; Enclosure lighting for power circuit; Key switch (local/remote) for power circuit; Motor heating for power circuit; External motor fan for power circuit; Voltmeter for power circuit; Door handle for main switch for power circuit; Circuit breaker for power circuit; Line contactor for power circuit; Ammeter for power circuit; Enclosure heating for power circuit; Motor choke for power circuit; Cable entry via the top for power circuit; Enclosure plinth for power circuit; Braking unit for power circuit; Door handle for circuit breaker for power circuit; Control terminals for control circuit; Adaptor for 115 V logic inputs for control circuit; Relay output C/O for control circuit; Isolated amplifier for control circuit

operating position: Vertical +/- 10 degree

colour of enclosure: Light grey (RAL 7035)

height: 2162 mm

width: 600 mm

depth: 642 mm

net weight: 335 kg

Environment

electromagnetic compatibility: 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11

pollution degree: 2 conforming to EN/IEC 61800-5-1

IP degree of protection: IP23

vibration resistance: 0.6 gn (f= 10…200 Hz) conforming to EN/IEC 60068-2-6; 1.5 mm (f= 3…10 Hz) conforming to EN/IEC 60068-2-6; 3M3 conforming to EN/IEC 60721-3-3

shock resistance: 4 gn for 11 ms conforming to EN/IEC 60068-2-27; 3M2 conforming to EN/IEC 60721-3-3

noise level: 64 dB conforming to 86/188/EEC

environmental characteristic: Without condensation: 3C2 conforming to IEC 60721-3-3; Without condensation: 3K3 conforming to IEC 60721-3-3; Without condensation: 3S2 conforming to IEC 60721-3-3

relative humidity: 0…95 %

ambient air temperature for operation: 0…40 °C (without derating); 40…50 °C (with current derating of 1.2 % per °C)

ambient air temperature for storage: -25…70 °C

volume of cooling air: 600 m3/h

operating altitude: <= 1000 m without derating; 1000...3000 m with current derating 1 % per 100 m

standards: EN 55011 class A group 2; EN 61800-3 environments 1 category C3; EN/IEC 61800-5-1; EN/IEC 61800-3; EN 61800-3 environments 2 category C3

product certifications: GOST; ATEX

marking: CE