Skip to main content

Schneider-Electric
ABL8BUF24400

buffer module - 24..28.8 V DC - 40 A - for power supply
Net discounted price 307.93 EUR
Available when ordered (delivery time: 50 working day(s))
Barcode: 3389119406819
Tariff code: 8538909999

Link to the manufacturers site: ABL8BUF24400 - buffer module - 24..28.8 V DC - 40 A - for power supply

Main

Range of produc: Phaseo

Product or component type: Buffer module

Input voltage: 24...28.8 V DC

Output voltage: (Uin-0.25) V in nominal mode DC; (Uin-1) V in buffer mode DC

Maximum output current: 40 A

Holding time: 0.1 s at 40 A; 6 s at 0.5 A

Maximum output current: 40 A

Complementary

Input voltage limits: 22...30 V

maximum power dissipation in W: 15 W

Activation threshold: (Uin-1) V and 22 V min

Charging time: 25 s

Number of output channels: 1

Holding current: 20 A; 15 A; 4 A; 5 A; 7 A; 6 A; 3 A; 10 A; 2 A; 30 A; 35 A; 40 A; 8 A; 1 A; 25 A

Current consumption: 0.6 A on load; 0.1 mA no load; <= 40.6 A

Output protection type: Against overload, protection technology: > 45 A; Against short-circuits, protection technology: power-supplied mode, automatic reset; Against undervoltage, protection technology: tripping if U < 19 V

Connections - terminals: For input connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² AWG 20...AWG 8; For output connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² AWG 20...AWG 8; For diagnostic relay: removable screw terminal block, connection capacity: 1 x 2.5 mm² AWG 14

Fixing mode: By clips on 35 mm symmetrical DIN rail, operating position: horizontal; By clips on 35 mm symmetrical DIN rail, operating position: vertical

Output coupling: Parallel

Operating altitude: 2000 m

Marking: CE

Name of test: Electrostatic discharges conforming to IEC 61000-4-2; Emission conforming to IEC 61000-6-3; Induced electromagnetic field conforming to IEC 61000-4-6 level 3; Radiated electromagnetic field conforming to IEC 61000-4-3 level 3; Rapid transient conforming to IEC 61000-4-4 level 3; Surge conforming to IEC 61000-4-5 level 2; Conducted/radiated emissions conforming to EN 55022 class B, 20 %

Local signalling: 1 LED (green) for buffer ready; 1 relay for buffer ready

Net weight: 1.2 kg

Holding time: 3 s; 4 s; 0.4 s; 1.5 s; 0.3 s; 0.2 s; 0.5 s; 6 s; 2 s; 0.1 s; 0.6 s; 1 s

Holding solution: Use of buffer modules

Compatibility code: ABL8B

Environment

product certifications: RCM; EAC

Standards: UL 508; CSA C22.2 No 60950-1

ambient air temperature for operation: -25…60 °C

Ambient air temperature for storage: -40…85 °C

Environmental characteristic: EMC conforming to IEC 61000-6-3; EMC conforming to IEC 61000-6-2; Safety conforming to IEC 60950-1; Safety conforming to EN/IEC 61204-3

IP degree of protection: IP20 conforming to IEC 60529

Dielectric strength: 500 V between input and ground; 500 V between output and ground

Overvoltage category: Class II conforming to VDE 0106-1

Relative humidity: 0…90 % during operation; 0…95 % during storage

MTBF reliability: 1119603 H at 24 V DC with UTE C80-810 calculation method

Vibration resistance: 2 gn (f= 11.9…150 Hz) conforming to IEC 61131-2; 3.5 mm (f= 3…11.9 Hz) conforming to IEC 61131-2

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 11.5 cm

Package 1 Width: 17.0 cm

Package 1 Length: 18.2 cm

Package 1 Weight: 1.401 kg

Unit Type of Package 2: P06

Number of Units in Package 2: 60

Package 2 Height: 80.0 cm

Package 2 Width: 80.0 cm

Package 2 Length: 60.0 cm

Package 2 Weight: 97.06 kg

Offer Sustainability

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free: Yes

China RoHS Regulation: X

RoHS exemption information: Yes

PVC free: Yes

© 2018 Alplan Kft.