Schneider-Electric
LRD226
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: LRD226 - TeSys LRD thermal overload relays - 16...24 A - class 10A
Main
range: TeSys; TeSys Deca
product name: TeSys LRD; TeSys Deca
product or component type: Differential thermal overload relay
device short name: LRD
relay application: Motor protection
product compatibility: LC1D32; LC1D25; LC1D38
network type: DC; AC
thermal overload class: Class 10A conforming to IEC 60947-4-1
thermal protection adjustment range: 16…24 A
[Ui] rated insulation voltage: Power circuit: 600 V conforming to CSA; Power circuit: 600 V conforming to UL; Power circuit: 690 V conforming to IEC 60947-4-1
Complementary
network frequency: 0...400 Hz
mounting support: Plate, with specific accessories; Rail, with specific accessories; Under contactor
tripping threshold: 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
auxiliary contact composition: 1 NO + 1 NC
[Ith] conventional free air thermal current: 5 A for signalling circuit
permissible current: 1.5 A at 240 V AC-15 for signalling circuit; 0.1 A at 250 V DC-13 for signalling circuit
[Ue] rated operational voltage: 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
associated fuse rating: 4 A gG for signalling circuit; 4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage: 6 kV
phase failure sensitivity: Tripping current 130 % of Ir on two phase, the last one at 0
control type: Red push-button: stop; Blue push-button: reset
temperature compensation: -20…60 °C
connection pitch: 17.5 mm
connections - terminals: Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end; Power circuit: lugs-ring terminals
tightening torque: Control circuit: 1.7 N.m - on screw clamp terminals; Power circuit: 2.3 N.m - on lugs-ring terminals M4
height: 66 mm
width: 45 mm
depth: 70 mm
net weight: 0.124 kg
compatibility code: LRD
Environment
protective treatment: TH conforming to IEC 60068
IP degree of protection: IP20 conforming to IEC 60529
ambient air temperature for operation: -20…60 °C without derating conforming to IEC 60947-4-1
ambient air temperature for storage: -60…70 °C
flame retardance: V1 conforming to UL 94
mechanical robustness: Vibrations: 6 Gn conforming to IEC 60068-2-6; Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
dielectric strength: 1.89 kV at 50 Hz conforming to IEC 60947-1
standards: EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; GB/T 14048.4; GB/T 14048.5; EN 50495
product certifications: IEC; UL; CSA; CCC; EAC; BV; RINA; DNV-GL; LROS (Lloyds register of shipping); ATEX INERIS; UKCA
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure: ENVPEP080206EN
Circularity Profile: ENVEOLI0802006
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.