Schneider-Electric
GV2ME086
Tariff code: 8536201090
Link to the manufacturers site: GV2ME086 - Motor circuit breaker, TeSys GV2, 3P, 2.5-4 A, thermal magnetic, lugs terminals
Main
Range: TeSys Deca
Range of produc: TeSys GV2
Product name: TeSys GV2; TeSys Deca
Product or component type: Motor circuit breaker
Device short name: GV2ME
Device application: Motor protection
Trip unit technology: Thermal-magnetic
Complementary
Poles description: 3P
Network type: AC
Utilisation category: Category A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1; AC-3e conforming to IEC 60947-4-1
Network frequency: 50/60 Hz conforming to IEC 60947-4-1
Fixing mode: 35 mm symmetrical DIN rail: clipped; Panel: screwed (with adaptor plate)
Motor power kW: 1.1 kW at 400/415 V AC 50/60 Hz; 1.5 kW at 400/415 V AC 50/60 Hz; 1.5 kW at 500 V AC 50/60 Hz; 2.2 kW at 500 V AC 50/60 Hz; 3 kW at 690 V AC 50/60 Hz; 2.2 kW at 690 V AC 50/60 Hz
Breaking capacity: 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity: 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2; 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
control type: Push-button
[In] rated current: 4 A
Thermal protection adjustment range: 2.5…4 A conforming to IEC 60947-4-1
Magnetic tripping current: 51 A
[Ith] conventional free air thermal current: 4 A conforming to IEC 60947-4-1
[Ue] rated operational voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947-2
Phase failure sensitivity: Yes conforming to IEC 60947-4-1
Suitability for isolation: Yes conforming to IEC 60947-1 § 7-1-6
Power dissipation per pole: 2.5 W
Mechanical durability: 100000 cycles
Electrical durability: 100000 cycles for AC-3 at 415 V In; 100000 cycles for AC-3e at 415 V In
Maximum operating rate: 25 cyc/h
Rated duty: Continuous conforming to IEC 60947-4-1
Direct connector: Without
Width: 45 mm
height: 89 mm
Depth: 78.5 mm
Net weight: 0.26 kg
Colour: Dark grey
Compatibility code: GV2ME
Connection pitch: 13.5 mm without spreader
Environment
Standards: EN/IEC 60947-2; EN/IEC 60947-4-1
product certifications: CCC; UL; CSA; EAC; ATEX; LROS (Lloyds register of shipping); BV; RINA; DNV-GL; UKCA
IK degree of protection: IK04
IP degree of protection: IP20 conforming to IEC 60529
Climatic withstand: conforming to IACS E10
Ambient air temperature for storage: -40…80 °C
Fire resistance: 960 °C conforming to IEC 60695-2-11
Ambient air temperature for operation: -20…60 °C
Mechanical robustness: Shocks: 30 Gn for 11 ms; Vibrations: 5 Gn, 5...150 Hz
Operating altitude: 2000 m
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 8.636 cm
Package 1 Width: 9.398 cm
Package 1 Length: 5.08 cm
Package 1 Weight: 258.55 g
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant with Exemptions
Mercury free: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP121004
Circularity Profile: ENVEOLI121004
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.