Skip to main content

Schneider-Electric
RMPT53BD

temperature transmitter - 0..250 °C/32..482 °F - for Optimum Pt100 probes
Net discounted price 68.03 EUR
Available when ordered (delivery time: 8 working day(s))
Barcode: 3389110108996
Tariff code: 8543709099

Link to the manufacturers site: RMPT53BD - temperature transmitter - 0..250 °C/32..482 °F - for Optimum Pt100 probes

Main

Range of produc: Harmony Analog

Product or component type: Converter for Optimum Pt100 probes

Analogue input type: Temperature probe 0...250 °C/32...482 °F Pt 100 2, 3 or 4 wires

Analogue output type: Current 4...20 mA <= 500 Ohm; Voltage 0...10 V >= 100 kOhm

Complementary

Protection type: Short-circuit protection on output; Reverse polarity protection on power supply; Overvoltage protection on output (+/- 30 V); Reverse polarity protection on output

Analogue output voltage: -15...-11 V when no input or input wire broken; 11...15 V when no input or input wire broken

Analogue output current: -30…0 mA when no input or input wire broken; 22…30 mA when no input or input wire broken

[Us] rated supply voltage: 24 V DC non isolated +/- 20 %

Current consumption: <= 40 mA for voltage output; <= 60 mA for current output

Local signalling: LED (green) for power ON

Measurement error: +/- 0.5 % of full scale (3 or 4 wires) at 20 °C; +/- 1 % of full scale (2 wires) at 20 °C; +/- 10 % of full scale at 20 °C (electromagnetic interference of 10 V/m)

Repeat accuracy: +/- 0.2 % full scale at 20 °C; +/- 0.6 % full scale at 60 °C

Temperature coefficient: 150 ppm/°C

Maximum wiring resistance: 0.2 Ohm connection in 2 wires

clamping connection capacity: 1 x 2.5 mm²; 2 x 1.5 mm²

Tightening torque: 0.6…1.1 N.m

Marking: CE

Surge withstand: 0.5 kV during 1.2/50 µs conforming to IEC 61000-4-5

[Ui] rated insulation voltage: 2000 V

Fixing mode: Clip-on (35 mm symmetrical DIN rail); Fixed (mounting plate)

Safety reliability data: MTTFd = 43.9 years; B10d = 40564

Net weight: 0.12 kg

Environment

Electromagnetic compatibility: Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2; Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2

Standards: DIN 43760; EN/IEC 60751; EN/IEC 60947-1; EN/IEC 60584-1

product certifications: UL; CSA; GL

IP degree of protection: IP20 (terminal block); IP50 (housing)

Fire resistance: 850 °C conforming to IEC 60695-2-1; 850 °C conforming to UL

Shock resistance: 50 gn for 11 ms conforming to IEC 60068-2-27

Vibration resistance: 5 gn (f= 10…100 Hz) conforming to IEC 60068-2-6

Resistance to fast transients: 1 kV (on input-output) conforming to IEC 61000-4-4; 2 kV (on power supply) conforming to IEC 61000-4-4

Disturbance radiated/conducted: CISPR 22 group 1 - class B; CISPR 11

Ambient air temperature for storage: -40…85 °C

Ambient air temperature for operation: 0…50 °C mounting side by side; 0…60 °C 2 cm spacing

Pollution degree: 2 conforming to IEC 60664-1

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 2.7 cm

Package 1 Width: 8.2 cm

Package 1 Length: 8.5 cm

Package 1 Weight: 102.0 g

Unit Type of Package 2: S02

Number of Units in Package 2: 47

Package 2 Height: 15 cm

Package 2 Width: 30 cm

Package 2 Length: 40 cm

Package 2 Weight: 5.25 kg

Unit Type of Package 3: P06

Number of Units in Package 3: 752

Package 3 Height: 75 cm

Package 3 Width: 40 cm

Package 3 Length: 80 cm

Package 3 Weight: 101.704 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free: Yes

China RoHS Regulation: X

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP1607005EN

Circularity Profile: ENVEOLI1607005EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

© 2018 Alplan Kft.