Schneider-Electric
RMPT30BD
Tariff code: 8543709099
Link to the manufacturers site: RMPT30BD - temperature transmitter - 0..100 °C/32..212 °F - for Universal Pt100 probes
Main
Range of produc: Harmony Analog
Product or component type: Converter for Universal Pt100 probes
Analogue input type: Temperature probe 0...100 °C/32..212 °F Pt 100 2, 3 or 4 wires
Analogue output type: Current 0...20 mA <= 500 Ohm; Current 4...20 mA <= 500 Ohm; Voltage 0...10 V >= 100 kOhm
Complementary
Protection type: Reverse polarity protection on power supply; Short-circuit protection on output; Overvoltage protection on output (+/- 30 V); Reverse polarity protection on output
Analogue output voltage: -15...-11 V when no input or input wire broken; 11...15 V when no input or input wire broken
Analogue output current: -30…0 mA when no input or input wire broken; 22…30 mA when no input or input wire broken
[Us] rated supply voltage: 24 V DC non isolated +/- 20 %
Current consumption: <= 40 mA for voltage output; <= 60 mA for current output
Local signalling: LED (green) for power ON
Measurement error: +/- 0.5 % of full scale (3 or 4 wires) at 20 °C; +/- 1 % of full scale (2 wires) at 20 °C; +/- 10 % of full scale at 20 °C (electromagnetic interference of 10 V/m)
Repeat accuracy: +/- 0.2 % full scale at 20 °C; +/- 0.6 % full scale at 60 °C
Temperature coefficient: 150 ppm/°C
Maximum wiring resistance: 0.2 Ohm connection in 2 wires
clamping connection capacity: 1 x 2.5 mm²; 2 x 1.5 mm²
Tightening torque: 0.6…1.1 N.m
Marking: CE
Surge withstand: 0.5 kV during 1.2/50 µs conforming to IEC 61000-4-5
[Ui] rated insulation voltage: 2000 V
Fixing mode: Clip-on (35 mm symmetrical DIN rail); Fixed (mounting plate)
Safety reliability data: MTTFd = 32.9 years; B10d = 30437
Net weight: 0.12 kg
Environment
Electromagnetic compatibility: Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2; Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Standards: DIN 43760; EN/IEC 60751; EN/IEC 60947-1; EN/IEC 60584-1
product certifications: GL; UL; CSA
IP degree of protection: IP20 (terminal block); IP50 (housing)
Fire resistance: 850 °C conforming to IEC 60695-2-1; 850 °C conforming to UL
Shock resistance: 50 gn for 11 ms conforming to IEC 60068-2-27
Vibration resistance: 5 gn (f= 10…100 Hz) conforming to IEC 60068-2-6
Resistance to fast transients: 1 kV (on input-output) conforming to IEC 61000-4-4; 2 kV (on power supply) conforming to IEC 61000-4-4
Disturbance radiated/conducted: CISPR 22 group 1 - class B; CISPR 11
Ambient air temperature for storage: -40…85 °C
Ambient air temperature for operation: 0…50 °C mounting side by side; 0…60 °C 2 cm spacing
Pollution degree: 2 conforming to IEC 60664-1
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 2.7 cm
Package 1 Width: 8.2 cm
Package 1 Length: 8.5 cm
Package 1 Weight: 108.0 g
Unit Type of Package 2: S02
Number of Units in Package 2: 47
Package 2 Height: 15 cm
Package 2 Width: 30 cm
Package 2 Length: 40 cm
Package 2 Weight: 5.557 kg
Unit Type of Package 3: P06
Number of Units in Package 3: 752
Package 3 Height: 75 cm
Package 3 Width: 60 cm
Package 3 Length: 80 cm
Package 3 Weight: 98 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
China RoHS Regulation: X
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP1607005EN
Circularity Profile: ENVEOLI1607005EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins