Schneider-Electric
RM35TM50MW
Tariff code: 8536490099
Link to the manufacturers site: RM35TM50MW - motor voltage and temperature control relay - RM35-T - 24..240 V AC/DC - 2 NO
Main
Range of produc: Harmony Control Relays
Relay type: Motor temperature control relay
Product or component type: Motor temperature control relay
Product specific application: For 3-phase supply
Relay name: RM35TM
Relay monitored parameters: Phase sequence; Motor temperature via PTC probe; Phase failure detection
Time delay type: Fixed 0.3 s
Switching capacity in VA: 1250 VA
Measurement range: 208...480 V voltage AC; 0...20 Ohm short-circuit detection
Contacts type and composition: 2 NO
Connections - terminals: Screw connectors
[Uc] control circuit voltage: 24...240 V
[In] rated current: 5 A
Complementary
Reset time: 10000 ms output
Maximum switching voltage: 250 V AC; 250 V DC
Minimum switching current: 10 mA at 5 V DC
Maximum switching current: 5 A AC; 5 A DC
Supply voltage limits: 20.4…264 V AC; 20.4…264 V DC
Power consumption in VA: 0…4 VA at 24...240 V AC
Maximum power consumption in W: 0.5 W DC
control circuit frequency: 50...60 Hz +/- 10 %
Resistance across terminals: 602 mOhm
Output contacts: 2 NO
Nominal output current: 5 A
Measurement voltage limits: 176…528 V AC
run-up delay at power-up: 500 ms
Voltage range: 176...528 V
Response time: > 50 ms (input Y1 (contact Y1-T1) and push-button)
[Uc] control circuit voltage: <= 3.6 V of temperature control circuit (T1-T2 terminals open)
Short-circuit current: 0.007 A temperature sensing circuit (T1-T2 terminals short circuited)
Maximum resistance: 1500 Ohm for temperature sensor at 20 °C
Tripping threshold: 3100 Ohm +/- 10 % for temperature control circuit
Reset threshold: 1650 Ohm +/- 10 % for temperature control circuit
Marking: CE
Overvoltage category: III conforming to IEC 60664-1
Insulation resistance: > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5; > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1; > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5; > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1; > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5; > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1
[Ui] rated insulation voltage: 400 V conforming to IEC 60664-1
Supply frequency: 50/60 Hz +/- 10 %
Operating position: Any position without derating
Connections - terminals: Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end; Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Tightening torque: 0.6…1 N.m conforming to IEC 60947-1
Housing material: Self-extinguishing plastic
Local signalling: LED (green) for power ON; LED (yellow) for phase of relay (R2); LED (yellow) for temperature of relay (R1)
Mounting support: 35 mm symmetrical DIN rail conforming to IEC 60715
Electrical durability: 10000 cycles
Mechanical durability: 30000000 cycles
Operating rate: <= 360 operations/hour full load
Utilisation category: AC-12 conforming to IEC 60947-5-1; AC-13 conforming to IEC 60947-5-1; AC-14 conforming to IEC 60947-5-1; AC-15 conforming to IEC 60947-5-1; DC-12 conforming to IEC 60947-5-1; DC-13 conforming to IEC 60947-5-1
Width: 35 mm
Net weight: 0.13 kg
Compatibility code: RM3
Environment
Immunity to microbreaks: 20 ms at 20.4 V
Electromagnetic compatibility: Emission standard for industrial environments conforming to IEC 61000-6-4; Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3; Immunity for industrial environments conforming to IEC 61000-6-2
Standards: IEC 60255-6; IEC 60034-11-2
product certifications: GL; UL; GOST; C-Tick; CSA
Directives: 73/23/EEC - low voltage directive; 89/336/EEC - electromagnetic compatibility
Ambient air temperature for storage: -40…70 °C
Ambient air temperature for operation: -20…50 °C
Relative humidity: 95 % at 55 °C conforming to IEC 60068-2-30
Vibration resistance: 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6; 1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1
Shock resistance: 15 gn for 11 ms conforming to IEC 60255-21-1
IP degree of protection: IP20 (terminals) conforming to IEC 60529; IP30 (casing) conforming to IEC 60529
Pollution degree: 3 conforming to IEC 60664-1
Dielectric test voltage: 2 kV, 1 min AC 50 Hz
Non-dissipating shock wave: 4 kV
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 4.5 cm
Package 1 Width: 7.8 cm
Package 1 Length: 9.6 cm
Package 1 Weight: 131.0 g
Unit Type of Package 2: S03
Number of Units in Package 2: 48
Package 2 Height: 30.0 cm
Package 2 Width: 30.0 cm
Package 2 Length: 40.0 cm
Package 2 Weight: 7.0 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
China RoHS Regulation: X
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP1504008EN
Circularity Profile: ENVEOLI1504008EN
© 2018 Alplan Kft.