RM35LM33MW

liquid level control relay RM35-L - 24..240 V AC/DC
Net discounted price 65.64 EUR
Available when ordered (delivery time: 22 working day(s))
Barcode: 3389119405232
Tariff code: 8536490099

Link to the manufacturers site: RM35LM33MW - liquid level control relay RM35-L - 24..240 V AC/DC

Main

Range of produc: Harmony Control Relays

Relay type: Level control relay

Product or component type: Level control relay

Relay name: RM35L

Relay monitored parameters: Detection by resistive probes

Time delay type: Adjustable 0.1...5 s, +/- 10 %

Switching capacity in VA: 1250 VA

Minimum switching current: 10 mA at 5 V DC

Maximum switching current: 5 A AC/DC

Maximum power consumption in VA: 5 VA AC

Measurement range: 250 Ohm...1 MOhm

Utilisation category: AC-12 conforming to IEC 60947-5-1; AC-13 conforming to IEC 60947-5-1; AC-14 conforming to IEC 60947-5-1; AC-15 conforming to IEC 60947-5-1; DC-12 conforming to IEC 60947-5-1; DC-13 conforming to IEC 60947-5-1

Contacts type and composition: 2 C/O

Connections - terminals: Screw connectors

[Uc] control circuit voltage: 24...240 V

[In] rated current: 5 A

Complementary

Reset time: 1750 ms

Maximum switching voltage: 250 V AC/DC

Supply voltage limits: 20.4…264 V AC/DC

Control circuit voltage limits: - 15 % + 10 % Un

Maximum power consumption in W: 1.5 W DC

Output contacts: 2 C/O

Nominal output current: 5 A

run-up delay at power-up: 0.6 s

Measurement accuracy: +/- 10 % of the full scale value; +/- 20 % for the HS range

Repeat accuracy: +/- 2 % for time delay

Measurement error: 0.5 %/°C with temperature variation

Sensitivity scale: 0.25...5 kOhm LS (Low Sensitivity); 5...100 kOhm St (Standard Sensitivity); 50...1000 kOhm HS (High Sensitivity)

Sensitivity adjustment: 5…100 %

Maximum supply current for sensors: 1 mA

Cable capacitance: 1 nF at HS (High Sensitivity) for probe cable; 2.2 nF at St (Standard Sensitivity) for probe cable; 4.7 nF at LS (Low Sensitivity)

Marking: CE : 73/23/EEC; CE : EMC 89/336/EEC

Overvoltage category: III conforming to IEC 60664-1

Insulation resistance: > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5; > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1; > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5; > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1; > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5; > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1

[Ui] rated insulation voltage: 250 V conforming to IEC 60664-1

[Uimp] rated impulse withstand voltage: 4 kV conforming to IEC 60255-5; 4 kV conforming to IEC 60664-1; 4 kV conforming to IEC 61000-4-5

Operating position: Any position without derating

Connections - terminals: Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end; Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end

Tightening torque: 0.6…1 N.m conforming to IEC 60947-1

Housing material: Self-extinguishing plastic

Local signalling: LED (yellow) for relay ON; LED (green) for power ON; LED (yellow) for timer ON

Mounting support: 35 mm symmetrical DIN rail conforming to IEC 60715

Electrical durability: 100000 cycles

Mechanical durability: 30000000 cycles

Operating rate: <= 360 operations/hour full load

Safety reliability data: B10d = 170000; MTTFd = 182.6 years

Width: 35 mm

Functionality: Resistive probe detection

Compatibility code: RM3

Environment

Immunity to microbreaks: 100 ms DC; 90 ms AC

Electromagnetic compatibility: Emission standard for industrial environments conforming to IEC 61000-6-4; Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3; Immunity for industrial environments conforming to NF EN/IEC 61000-6-2

Standards: IEC 60255-6

product certifications: CSA; GL; UL; C-Tick; GOST

Ambient air temperature for storage: -40…70 °C

Ambient air temperature for operation: -20…50 °C

Relative humidity: 95 % at 55 °C conforming to IEC 60068-2-30

IP degree of protection: IP20 (terminals) conforming to IEC 60529; IP30 (casing) conforming to IEC 60529

Pollution degree: 3 conforming to IEC 60664-1

Dielectric test voltage: 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5; 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 4.700 cm

Package 1 Width: 7.800 cm

Package 1 Length: 9.700 cm

Package 1 Weight: 141.000 g

Unit Type of Package 2: S03

Number of Units in Package 2: 48

Package 2 Height: 30.000 cm

Package 2 Width: 30.000 cm

Package 2 Length: 40.000 cm

Package 2 Weight: 7.448 kg

Unit Type of Package 3: P06

Number of Units in Package 3: 384

Package 3 Height: 75.000 cm

Package 3 Width: 60.000 cm

Package 3 Length: 80.000 cm

Package 3 Weight: 65.660 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free: Yes

China RoHS Regulation: X

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP1504008EN