Schneider-Electric
RM35JA32MW
Tariff code: 8536490099
Link to the manufacturers site: RM35JA32MW - current control relay RM35-J - range 0.15..1.5 A
Main
Range of produc: Harmony Control Relays
Relay type: Current control relay
Product or component type: Current control relay
Relay name: RM35JA
Relay monitored parameters: Overcurrent or undercurrent detection
Time delay type: Adjustable 1...20 s, 0 + 10 % on energisation Ti; Adjustable 0.3...30 s, 0 + 10 % on crossing the threshold Tt
Switching capacity in VA: 1250 VA
Minimum switching current: 10 mA at 5 V DC
Maximum switching current: 5 A AC/DC
Maximum power consumption in VA: 3.5 VA AC
Measurement range: 0.15...1.5 A E1-M terminals; 0.5...5 A E2-M terminals; 1.5...15 A E3-M terminals; 150 mA...15 A current
Utilisation category: AC-12 conforming to IEC 60947-5-1; AC-13 conforming to IEC 60947-5-1; AC-14 conforming to IEC 60947-5-1; AC-15 conforming to IEC 60947-5-1; DC-12 conforming to IEC 60947-5-1; DC-13 conforming to IEC 60947-5-1; DC-14 conforming to IEC 60947-5-1
Contacts type and composition: 2 C/O
Connections - terminals: Screw connectors
[Uc] control circuit voltage: 24...240 V
[In] rated current: 5 A
Complementary
Reset time: 1500 ms time delay
Maximum switching voltage: 250 V AC/DC
Supply voltage limits: 20.4…264 V AC/DC
Control circuit voltage limits: - 15 % + 10 % Un
Maximum power consumption in W: 0.6 W DC
control circuit frequency: 40...70 Hz +/- 10 %
Resistance across terminals: 0.005 Ohm at E3-M terminals; 0.015 Ohm at E2-M terminals; 0.05 Ohm at E1-M terminals
Output contacts: 2 C/O
Nominal output current: 5 A
Maximum measuring cycle: 30 ms measurement cycle as true rms value
Hysteresis: 5…50 % of threshold setting
run-up delay at power-up: 0.3 s
Measurement accuracy: +/- 10 % of the full scale value
Repeat accuracy: +/- 0.5 % for input and measurement circuit; +/- 2 % for time delay
Measurement error: 0.05 %/°C with temperature variation; 1 by volt over the whole range with voltage variation
Polarity: No DC
Threshold setting: 10...100 %
Marking: CE : EMC 89/336/EEC; CE : 73/23/EEC
Overvoltage category: III conforming to IEC 60664-1
Insulation resistance: > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5; > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1; > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5; > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1; > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5; > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1
[Ui] rated insulation voltage: 250 V conforming to IEC 60664-1
Operating position: Any position without derating
Connections - terminals: Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end; Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Tightening torque: 0.6…1 N.m conforming to IEC 60947-1
Housing material: Self-extinguishing plastic
Local signalling: LED (green) for power ON; LED (yellow) for relay ON
Mounting support: 35 mm symmetrical DIN rail conforming to IEC 60715
Electrical durability: 100000 cycles
Mechanical durability: 30000000 cycles
Operating rate: <= 360 operations/hour full load
Safety reliability data: MTTFd = 296.8 years; B10d = 270000
Contacts material: Cadmium free
Width: 35 mm
Net weight: 0.13 kg
Functionality: Overcurrent or undercurrent in window mode
Compatibility code: RM3
Environment
Immunity to microbreaks: 50 ms
Electromagnetic compatibility: Emission standard for industrial environments conforming to IEC 61000-6-4; Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3; Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Standards: IEC 60255-6
product certifications: GL; UL; GOST; C-Tick; CSA
Ambient air temperature for storage: -40…70 °C
Ambient air temperature for operation: -20…50 °C
Relative humidity: 95 % at 55 °C conforming to IEC 60068-2-30
Vibration resistance: 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6; 1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1
Shock resistance: 15 gn for 11 ms conforming to IEC 60255-21-1
IP degree of protection: IP20 (terminals) conforming to IEC 60529; IP30 (casing) conforming to IEC 60529
Pollution degree: 3 conforming to IEC 60664-1
Dielectric test voltage: 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5; 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1
Non-dissipating shock wave: 4 kV conforming to IEC 60255-5; 4 kV conforming to IEC 60664-1; 4 kV conforming to IEC 61000-4-5
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 4.500 cm
Package 1 Width: 8.000 cm
Package 1 Length: 9.500 cm
Package 1 Weight: 145.000 g
Unit Type of Package 2: S03
Number of Units in Package 2: 48
Package 2 Height: 30.000 cm
Package 2 Width: 30.000 cm
Package 2 Length: 40.000 cm
Package 2 Weight: 7.735 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
China RoHS Regulation: X
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP1504008EN
Circularity Profile: ENVEOLI1504008EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.