Skip to main content

Schneider-Electric
LVR14250B40T

Anti Harmonic detuned reactor 25kvar 162Hz (2.7) 14% 60Hz 400V
Barcode: 3606480541612
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: LVR14250B40T - Anti Harmonic detuned reactor 25kvar 162Hz (2.7) 14% 60Hz 400V

Main

range: VarPlus

device short name: DR

product or component type: Detuned reactor

network frequency: 60 Hz

reactive power rating: 25 kvar for 400 V AC 60 Hz

network rated voltage: 400 V AC 60 Hz

tuning order: 2.7 - 162 Hz - 14 % - 60 Hz

Complementary

power losses: 200 W

value of inductance: 2.704 mH

inductance tolerance: - 5 % to 5 % per phase

fundamental current rating: 36.1 A

maximum current Irms: 36.8 A

electrical insulation class: Class H

[Ui] rated insulation voltage: 1.1 kV

dielectric test voltage: 4 kV 60 Hz 1 minute

[Imp] maximum permanent current: 1.12 x I1

harmonic current spectrum: 5.5 % x I3; 10.7 % x I5; 5.3 % x I7; 2.1 % x I11

dynamic withstand current: 2.2 x Isc

[Ith] conventional free air thermal current: 2 A at 250 V AC 50 Hz

type of installation: Indoor installation

type of cooling: Forced convection

connections - terminals: Pad terminal

fixing center: 200 x 125 mm

height: 220 mm

width: 240 mm

depth: 160 mm

net weight: 18 kg

Environment

standards: IEC 60068

IP degree of protection: IP00

operating altitude: <= 2000 m

ambient air temperature for operation: 0…55 °C at <= 1000 m; 0…50 °C at > 1000...2000 m

average ambient air temperature for operation: 50 °C at <= 1000 m (average over 24 hours) ; 40 °C at <= 1000 m (average over 1 year) ; 45 °C at > 1000...2000 m (average over 24 hours) ; 35 °C at > 1000...2000 m (average over 1 year)

climatic withstand: Relative humidity: 20...80 %; Salt mist (400 V/50 Hz) : 250 hours

© 2018 Alplan Kft.