Skip to main content

Schneider-Electric
LD1LD030M

TeSys Integral - contactor breaker - 63 A AC-43 - 220...230 V AC coil
Barcode: 3389110181128
Tariff code: 8536508090

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: LD1LD030M - TeSys Integral - contactor breaker - 63 A AC-43 - 220...230 V AC coil

Main

Range of product: Integral 63

Range: TeSys

Product name: TeSys Integral 63

Product or component type: Contactor breaker

Device short name: LD1LD

Complementary

Utilisation category: AC-43

Poles description: 3P

[Ue] rated operational voltage: 690 V AC 50/60 Hz

[Ie] rated operational current: 63 A AC AC-43

[Ith] conventional free air thermal current: 63 A (at 40 °C)

Motor power kW: 15 kW at 220...240 V AC 50/60 Hz; 30 kW at 400 V AC 50/60 Hz; 33 kW at 415 V AC 50/60 Hz; 37 kW at 500 V AC 50/60 Hz; 55 kW at 660 V AC 50/60 Hz; 33 kW at 440 V AC 50/60 Hz

[Uc] control circuit voltage: 220...230 V AC 50 Hz

Control type: Knob black front

Irms rated making capacity: 756 A conforming to IEC 60947-4; 946 A conforming to IEC 60947-4

[Ipk] rated peak withstand current: 105 kA conforming to IEC 60947-2

Breaking capacity: Icu 10 kA at 600...690 V (cos φ 0.5) conforming to IEC 60947-2; Icu 30 kA at 480...525 V (cos φ 0.25) conforming to IEC 60947-6-2; Icu 50 kA at <= 440 V (cos φ 0.25) conforming to IEC 60947-2

[Ics] rated service breaking capacity: 10 kA at 600...690 V conforming to IEC 60947-2; 35 kA at 480...525 V conforming to IEC 60947-2; 50 kA at <= 440 V conforming to IEC 60947-2

Maximum breaking time: 4 ms

Thermal stress limit: 300000 A².s

[Uimp] rated impulse withstand voltage: 8 kV conforming to IEC 60947-4

Control circuit voltage limits: 0.25...0.7 Uc drop-out 55 °C; 0.85...1.1 Uc operation 55 °C

[Ui] rated insulation voltage: 690 V conforming to IEC 60947-1

Inrush power in VA: 375 VA 50 Hz (at 20 °C)

Hold-in power consumption in VA: 25 VA (at 20 °C)

Heat dissipation: 5 W at 32 A per pole, hot state for power circuit; 7 W at 50 A per pole, hot state for power circuit; 9 W at 63 A per pole, hot state for power circuit; 4.4 W at 25 A per pole, hot state for power circuit; 5.8 W at 40 A per pole, hot state for power circuit; 8 W at 50 Hz for control circuit

Operating time: 12...35 ms AC network closing at 20 °C for control circuit; 7...20 ms AC network opening at 20 °C for control circuit

Electrical durability: 1 Mcycles on AC-3 3 kA at 415 V - after 1 cycle O-CO-r-CO at Isc; 0.9 Mcycles on AC-3 10 kA at 415 V - after 1 cycle O-CO-r-CO at Isc; 0.6 Mcycles on AC-3 25 kA at 415 V - after 1 cycle O-CO-r-CO at Isc; 0.5 Mcycles on AC-3 35 kA at 415 V - after 1 cycle O-CO-r-CO at Isc; 0.2 Mcycles on AC-3 50 kA at 415 V - after 1 cycle O-CO-r-CO at Isc

Mechanical durability: 1.2 Mcycles

Connections - terminals: Power circuit: screw clamp terminals 1 cable(s) 6…50 mm² - flexible - without cable end; Power circuit: screw clamp terminals 2 cable(s) 6…25 mm² - flexible - without cable end; Power circuit: screw clamp terminals 1 cable(s) 6…25 mm² - flexible - with cable end; Power circuit: screw clamp terminals 2 cable(s) 6…25 mm² - flexible - with cable end; Power circuit: screw clamp terminals 1 cable(s) 6…50 mm² - solid

Tightening torque: Power circuit: 6 N.m - on screw clamp terminals

Width: 90 mm

Height: 243 mm

Depth: 192 mm

Net weight: 3.7 kg

Compatibility code: LD1LD

Environment

Standards: IEC 60204-1; BS 5424; NF C 79-100; IEC 60158-1; IEC 60947-4; NF C 63-110; VDE 0171; VDE 471; NF C 63-120; NF C 63-650; VDE 0110; NF C 20-040; IEC 60947-1; BS 4941; NBN; IEC 60947-2; VDE 0100; NEN; VDE 0660; VDE 0113; IEC 60204-2; BS 4752; NF C 63-130; IEC 60364; VDE 0170

Product certifications: ASEFA; RINA; DNV; SETI; LROS (Lloyds register of shipping); BV; USSR; GL; SCC; ASTA; UL; NKK; OVE; NEMKO; CSA; ASE; DEMKO

Protective treatment: TH

Ambient air temperature for operation: -20…60 °C

Ambient air temperature for storage: -40…80 °C

Mechanical robustness: Vibrations de-energised: 3 Gn, 1...300 Hz; Vibrations energised: 3 Gn, 1...300 Hz; Shocks de-energised: 8 Gn for 11 ms; Shocks energised: 8 Gn for 11 ms

IP degree of protection: IP20 B conforming to IEC 60144; IP20 B conforming to IEC 60529

Operating altitude: 3000 m without derating

Packing Units

Unit Type of Package 1: Db

Number of Units in Package 1: 1

Package 1 Height: 23 cm

Package 1 Width: 14.5 cm

Package 1 Length: 30.4 cm

Package 1 Weight: 4.023 kg

Unit Type of Package 2: P06

Number of Units in Package 2: 8

Package 2 Height: 75 cm

Package 2 Width: 60 cm

Package 2 Length: 80 cm

Package 2 Weight: 32.184 kg

Offer Sustainability

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Mercury free: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information

RoHS exemption information: Yes

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

© 2018 Alplan Kft.