Schneider-Electric
LC3D150P7
Tariff code: 8536490099
Link to the manufacturers site: LC3D150P7 - TeSys D - star delta starter - 3 x 3P (3 NO) - 150 A - 230 V AC coil
Main
Range of produc: TeSys Deca
Range: TeSys
Product name: TeSys Deca
Product or component type: Star delta starter
Device short name: LC3D
contactor application: Motor control
utilisation category: AC-3
device presentation: Pre-wired
Poles description: 3 x 3P
Pole contact composition: 3 x 3 NO
[Ue] rated operational voltage: Power circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current: 150 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Motor power kW: 132 kW at 380/400 V AC 50/60 Hz; 132 kW at 415 V AC 50/60 Hz; 147 kW at 440 V AC 50/60 Hz; 75 kW at 220/230 V AC 50/60 Hz
Control circuit type: AC at 50/60 Hz
[Uc] control circuit voltage: 230 V AC 50/60 Hz
Auxiliary contact composition: 1 NC for KM1 star contactor; 1 NC for KM2 line contactor; 1 NO for KM3 delta contactor
[Uimp] rated impulse withstand voltage: 8 kV conforming to IEC 60947
Overvoltage category: III
[Ui] rated insulation voltage: Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified; Power circuit: 1000 V conforming to IEC 60947-4-1; Signalling circuit: 1000 V conforming to IEC 60947-1
Electrical durability: 0.85 Mcycles 150 A AC-3 at Ue <= 440 V
mounting support: Plate
Standards: EN 60947-4-1; IEC 60947-4-1; EN 60947-5-1; CSA C22.2 No 14; UL 508; IEC 60947-5-1
product certifications: RINA; UL; GOST; DNV; CSA; CCC; LROS (Lloyds register of shipping); GL; BV
Complementary
Connections - terminals: Power circuit: connector 1 10…120 mm² - cable stiffness: flexible without cable end; Power circuit: connector 2 10…50 mm² - cable stiffness: flexible without cable end; Power circuit: connector 1 10…120 mm² - cable stiffness: flexible with cable end; Power circuit: connector 2 10…50 mm² - cable stiffness: flexible with cable end; Power circuit: connector 1 10…120 mm² - cable stiffness: solid without cable end; Power circuit: connector 2 10…50 mm² - cable stiffness: solid without cable end; Control circuit: connector 1 1…2.5 mm² - cable stiffness: flexible without cable end; Control circuit: connector 2 1…2.5 mm² - cable stiffness: flexible without cable end; Control circuit: connector 1 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: connector 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: connector 1 1…2.5 mm² - cable stiffness: solid without cable end; Control circuit: connector 2 1…2.5 mm² - cable stiffness: solid without cable end
Tightening torque: Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6...8 mm; Control circuit: 1.2 N.m - on connector - with screwdriver flat Ø 6 mm; Control circuit: 1.2 N.m - on connector - with screwdriver Philips No 2
Mechanical durability: 8 Mcycles
Maximum operating rate: 30 cyc/h 60 °C
Starting time: 30 s
Coil technology: Without built-in suppressor module
Control circuit voltage limits: Drop-out: 0.3...0.5 Uc at 50/60 Hz (at <55 °C); Operational: 0.8...1.15 Uc at 50/60 Hz (at <55 °C)
Inrush power in VA: 280…350 VA 60 Hz cos phi 0.9 (at 20 °C); 280…350 VA 50 Hz cos phi 0.9 (at 20 °C)
Hold-in power consumption in VA: 2…18 VA 60 Hz cos phi 0.9 (at 20 °C); 2…18 VA 50 Hz cos phi 0.9 (at 20 °C)
Heat dissipation: 3…4.5 W at 50/60 Hz
Auxiliary contacts type: Mechanically linked conforming to IEC 60947-5-1 3 x 1 NO + 1 NC; Mirror contact conforming to IEC 60947-4-1 3 x 1 NC
Signalling circuit frequency: 25...400 Hz
Minimum switching current: 5 mA for signalling circuit
Switching voltage: 17 V for signalling circuit
Non-overlap time: 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact
Width: 450 mm
height: 555 mm
Depth: 205 mm
Net weight: 12.1 kg
Power range: 55…100 kW at 200…240 V 3 phases; 110…220 kW at 380…440 V 3 phases
Motor starter type: Star delta starter
Contactor coil voltage: 230 V AC standard
Environment
Insulation resistance: > 10 MOhm for signalling circuit
IP degree of protection: IP20 front face conforming to IEC 60529
Protective treatment: TH conforming to IEC 60068-2-30
Pollution degree: 3
Ambient air temperature for storage: -60…80 °C
Ambient air temperature for operation: -40…60 °C; 60…70 °C with derating
Operating altitude: 3000 m
Fire resistance: 850 °C conforming to IEC 60695-2-1
Flame retardance: V1 conforming to UL 94
Mechanical robustness: Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 4 Gn, 5...300 Hz; Shocks contactor closed: 15 Gn for 11 ms; Shocks contactor open: 6 Gn for 11 ms
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 35.0 cm
Package 1 Width: 67.0 cm
Package 1 Length: 77.0 cm
Package 1 Weight: 12.1 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant with Exemptions
Mercury free: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP060301EN
Circularity Profile: ENVEOLI100405
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
PVC free: Yes
© 2018 Alplan Kft.