Schneider-Electric
LC1D40AT7
Tariff code: 8536490099
Link to the manufacturers site: LC1D40AT7 - TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 40 A - 480 V AC 50/60 Hz coil
Main
Range: TeSys; TeSys Deca
Range of produc: TeSys Deca
Product or component type: Contactor
Device short name: LC1D
contactor application: Motor control; Resistive load
utilisation category: AC-4; AC-1; AC-3; AC-3e
Poles description: 3P
[Ue] rated operational voltage: Power circuit: <= 690 V AC 25...400 Hz; Power circuit: <= 300 V DC
[Ie] rated operational current: 60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit; 40 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; 40 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage: 480 V AC 60 Hz
Complementary
Motor power kW: 18.5 kW at 380...400 V AC 50/60 Hz (AC-3); 11 kW at 220...230 V AC 50/60 Hz (AC-3); 22 kW at 415...440 V AC 50/60 Hz (AC-3); 22 kW at 500 V AC 50/60 Hz (AC-3); 30 kW at 660...690 V AC 50/60 Hz (AC-3); 9 kW at 400 V AC 50/60 Hz (AC-4); 18.5 kW at 380...400 V AC 50/60 Hz (AC-3e); 11 kW at 220...230 V AC 50/60 Hz (AC-3e); 22 kW at 415...440 V AC 50/60 Hz (AC-3e); 22 kW at 500 V AC 50/60 Hz (AC-3e); 30 kW at 660...690 V AC 50/60 Hz (AC-3e)
Motor power hp: 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 10 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 30 hp at 575/600 V AC 50/60 Hz for 3 phases motors; 10 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 3 hp at 115 V AC 50/60 Hz for 1 phase motors; 30 hp at 460/480 V AC 50/60 Hz for 3 phases motors
Compatibility code: LC1D
Pole contact composition: 3 NO
Contact compatibility: M2
Protective cover: With
[Ith] conventional free air thermal current: 10 A (at 60 °C) for signalling circuit; 60 A (at 60 °C) for power circuit
Irms rated making capacity: 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity: 800 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current: 320 A 40 °C - 10 s for power circuit; 720 A 40 °C - 1 s for power circuit; 72 A 40 °C - 10 min for power circuit; 165 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit
Associated fuse rating: 10 A gG for signalling circuit conforming to IEC 60947-5-1; 80 A gG at <= 690 V coordination type 1 for power circuit; 80 A gG at <= 690 V coordination type 2 for power circuit
Average impedance: 1.5 mOhm - Ith 60 A 50 Hz for power circuit
Power dissipation per pole: 2.4 W AC-3; 5.4 W AC-1; 2.4 W AC-3e
[Ui] rated insulation voltage: Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified; Power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage category: III
Pollution degree: 3
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947
Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability: 6 Mcycles
Electrical durability: 1.4 Mcycles 60 A AC-1 at Ue <= 440 V; 1.5 Mcycles 40 A AC-3 at Ue <= 440 V; 1.5 Mcycles 40 A AC-3e at Ue <= 440 V
Control circuit type: AC at 60 Hz
Coil technology: Without built-in suppressor module
Control circuit voltage limits: 0.3...0.6 Uc (-40…70 °C):drop-out AC 60 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 60 Hz
Inrush power in VA: 140 VA 60 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA: 13 VA 60 Hz cos phi 0.3 (at 20 °C)
Heat dissipation: 4…5 W at 60 Hz
Operating time: 4...19 ms opening; 12...26 ms closing
Maximum operating rate: 3600 cyc/h 60 °C
Connections - terminals: Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end; Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: flexible without cable end; Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: flexible without cable end; Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: flexible with cable end; Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: flexible with cable end; Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: solid without cable end; Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: solid without cable end
Tightening torque: Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25…35 mm² hexagonal screw head 4 mm; Power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1…25 mm² hexagonal screw head 4 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2; Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition: 1 NO + 1 NC
Auxiliary contacts type: type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency: 25...400 Hz
Minimum switching voltage: 17 V for signalling circuit
Minimum switching current: 5 mA for signalling circuit
Insulation resistance: > 10 MOhm for signalling circuit
Non-overlap time: 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact
mounting support: Rail; Plate
Environment
Standards: CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 508; IEC 60335-1
product certifications: GOST; UL; CCC; CSA
IP degree of protection: IP20 front face conforming to IEC 60529
Protective treatment: TH conforming to IEC 60068-2-30
Climatic withstand: conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device: -40…60 °C; 60…70 °C with derating
Operating altitude: 0...3000 m
Fire resistance: 850 °C conforming to IEC 60695-2-1
Flame retardance: V1 conforming to UL 94
Mechanical robustness: Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (10 Gn for 11 ms)
height: 122 mm
Width: 55 mm
Depth: 120 mm
Net weight: 0.85 kg
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 6.2 cm
Package 1 Width: 13.7 cm
Package 1 Length: 15.2 cm
Package 1 Weight: 946.0 g
Unit Type of Package 2: S02
Number of Units in Package 2: 10
Package 2 Height: 15.0 cm
Package 2 Width: 30.0 cm
Package 2 Length: 40.0 cm
Package 2 Weight: 9.915 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP1503009EN
Circularity Profile: ENVEOLI1503009EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins