Skip to main content

Schneider-Electric
LC1D115004F7

TeSys D contactor - 4P(4 NO) - AC-1 - <= 440 V 200 A - 110 V AC 50 Hz coil
Barcode: 3389110882322
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: LC1D115004F7 - TeSys D contactor - 4P(4 NO) - AC-1 - <= 440 V 200 A - 110 V AC 50 Hz coil

Main

range of product: TeSys D

range: TeSys

product name: TeSys D

product or component type: Contactor

device short name: LC1D

contactor application: Resistive load

utilisation category: AC-1

poles description: 4P

pole contact composition: 4 NO

[Ue] rated operational voltage: Power circuit: <= 1000 V AC 25...400 Hz; Power circuit: <= 460 V DC

[Ie] rated operational current: 200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

control circuit type: AC at 50/60 Hz

[Uc] control circuit voltage: 110 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage: 8 kV conforming to IEC 60947

overvoltage category: III

[Ith] conventional free air thermal current: 200 A (at 60 °C) for power circuit

Irms rated making capacity: 1260 A at 440 V for power circuit conforming to IEC 60947

rated breaking capacity: 1100 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current: 250 A 40 °C - 10 min for power circuit; 550 A 40 °C - 1 min for power circuit; 950 A 40 °C - 10 s for power circuit; 1100 A 40 °C - 1 s for power circuit

associated fuse rating: 250 A gG at <= 690 V coordination type 1 for power circuit; 200 A gG at <= 690 V coordination type 2 for power circuit

average impedance: 0.6 mOhm - Ith 200 A 50 Hz for power circuit

[Ui] rated insulation voltage: Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 1000 V conforming to IEC 60947-4-1

electrical durability: 0.8 Mcycles 200 A AC-1 at Ue <= 440 V

power dissipation per pole: 24 W AC-1

protective cover: With

mounting support: Plate; Rail

standards: CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 508

product certifications: UL; BV; GL; CCC; LROS (Lloyds register of shipping); DNV; CSA; GOST; RINA; UKCA

connections - terminals: Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end; Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end; Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²solid without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end; Power circuit: connector 1 cable(s) 10…120 mm²flexible without cable end; Power circuit: connector 2 cable(s) 10…50 mm²flexible without cable end; Power circuit: connector 1 cable(s) 10…120 mm²flexible with cable end; Power circuit: connector 2 cable(s) 10…50 mm²flexible with cable end; Power circuit: connector 1 cable(s) 10…120 mm²solid without cable end; Power circuit: connector 2 cable(s) 10…50 mm²solid without cable end

tightening torque: Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 12 N.m - on connector hexagonal screw head 4 mm

operating time: 6...20 ms opening; 20...50 ms closing

safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

mechanical durability: 8 Mcycles

maximum operating rate: 2400 cyc/h 60 °C

Complementary

coil technology: Built-in bidirectional peak limiting diode suppressor

control circuit voltage limits: 0.3...0.5 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.15 Uc (-40…55 °C):operational AC 50/60 Hz; 1...1.15 Uc (55…70 °C):operational AC 50/60 Hz

inrush power in VA: 280…350 VA 60 Hz cos phi 0.8 (at 20 °C); 280…350 VA 50 Hz cos phi 0.8 (at 20 °C)

hold-in power consumption in VA: 2…18 VA 60 Hz cos phi 0.3 (at 20 °C); 2…18 VA 50 Hz cos phi 0.3 (at 20 °C)

heat dissipation: 3…8 W at 50/60 Hz

contact compatibility: M14

compatibility code: LC1D

Environment

IP degree of protection: IP20 front face conforming to IEC 60529

protective treatment: TH conforming to IEC 60068-2-30

pollution degree: 3

ambient air temperature for operation: -40…60 °C; 60…70 °C with derating

ambient air temperature for storage: -60…80 °C

operating altitude: 0...3000 m

fire resistance: 850 °C conforming to IEC 60695-2-1

flame retardance: V1 conforming to UL 94

mechanical robustness: Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 4 Gn, 5...300 Hz; Shocks contactor closed: 15 Gn for 11 ms; Shocks contactor open: 6 Gn for 11 ms

height: 158 mm

width: 150 mm

depth: 132 mm

net weight: 2.86 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

EU RoHS Directive: Compliant

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure: ENVPEP060301EN

Circularity Profile: ENVEOLI100405EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

PVC free: Yes

© 2018 Alplan Kft.