Schneider-Electric
LC1D096FLS207
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: LC1D096FLS207 - TeSys D contactor S207 - 3P (3NO) AC-3 9A <=440V - coil 110V DC low
Main
range of product: TeSys D
range: TeSys
product name: TeSys D
product or component type: Contactor
device short name: LC1D
contactor application: Motor control; Resistive load
utilisation category: AC-1; AC-3; AC-3e
poles description: 3P
pole contact composition: 3 NO
[Ue] rated operational voltage: Power circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current: 9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit; 9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
motor power kW: 2.2 kW at 220/230 V AC 50 Hz (AC-3); 4 kW at 380/400 V AC 50 Hz (AC-3); 4 kW at 415 V AC 50 Hz (AC-3); 4 kW at 440 V AC 50 Hz (AC-3); 5.5 kW at 500 V AC 50 Hz (AC-3); 5.5 kW at 660/690 V AC 50 Hz (AC-3); 2.2 kW at 220/230 V AC 50 Hz (AC-3e); 4 kW at 380/400 V AC 50 Hz (AC-3e); 4 kW at 415 V AC 50 Hz (AC-3e); 4 kW at 440 V AC 50 Hz (AC-3e); 5.5 kW at 500 V AC 50 Hz (AC-3e); 5.5 kW at 660/690 V AC 50 Hz (AC-3e)
control circuit type: DC low consumption
[Uc] control circuit voltage: 110 V DC
coil type: Low consumption
auxiliary contact composition: 1 NO + 1 NC
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947
overvoltage category: III
[Ith] conventional free air thermal current: 10 A (at 60 °C) for signalling circuit; 25 A (at 60 °C) for power circuit
Irms rated making capacity: 250 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1
rated breaking capacity: 250 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current: 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit; 105 A 40 °C - 10 s for power circuit; 210 A 40 °C - 1 s for power circuit; 30 A 40 °C - 10 min for power circuit; 61 A 40 °C - 1 min for power circuit
associated fuse rating: 10 A gG for signalling circuit conforming to IEC 60947-5-1; 25 A gG at <= 690 V coordination type 1 for power circuit; 20 A gG at <= 690 V coordination type 2 for power circuit
average impedance: 2.5 mOhm - Ith 25 A 50 Hz for power circuit
[Ui] rated insulation voltage: Power circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-1
electrical durability: 0.6 Mcycles 25 A AC-1 at Ue <= 440 V; 2 Mcycles 9 A AC-3 at Ue <= 440 V; 2 Mcycles 9 A AC-3e at Ue <= 440 V
power dissipation per pole: 1.56 W AC-1; 0.2 W AC-3; 0.2 W AC-3e
protective cover: With
mounting support: Rail; Plate
standards: EN/IEC 60947-4-1; EN/IEC 60947-5-1; EN 45545 R22 HL3; EN 45545 R26 HL3; DIN 5510-2
product certifications: IEC; CCC; EAC; UA; TR; UKCA
connections - terminals: Control circuit: lugs-ring terminals (external diameter: 8 mm) ; Power circuit: lugs-ring terminals (external diameter: 9.5 mm)
tightening torque: Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5; Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5; Power circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5; Power circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5
operating time: 55...75 ms closing; 16...32 ms opening
safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability: 30 Mcycles
maximum operating rate: 3600 cyc/h 60 °C
Complementary
coil technology: With integral suppression device
control circuit voltage limits: 0.1...0.25 Uc (-40…70 °C):drop-out DC; 0.7...1.25 Uc (-40…70 °C):operational DC
time constant: 37 ms
inrush power in W: 4 W at 20 °C
hold-in power consumption in W: 4 W at 20 °C
auxiliary contacts type: type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency: 25...400 Hz
minimum switching current: 5 mA for signalling circuit
minimum switching voltage: 17 V for signalling circuit
non-overlap time: 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact
insulation resistance: > 10 MOhm for signalling circuit
contact compatibility: M5
compatibility code: LC1D
Environment
IP degree of protection: IP20 front face conforming to IEC 60529
protective treatment: TH conforming to IEC 60068-2-30
pollution degree: 3
ambient air temperature for operation: -40…70 °C
ambient air temperature for storage: -60…80 °C
operating altitude: 0...3000 m
fire resistance: 850 °C conforming to IEC 60695-2-1
flame retardance: V0 conforming to UL 94
mechanical robustness: Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 4 Gn, 5...300 Hz; Shocks contactor open: 10 Gn for 11 ms; Shocks contactor closed: 15 Gn for 11 ms
height: 77 mm
width: 45 mm
depth: 95 mm
net weight: 0.32 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure: ENVPEP1501004EN
Circularity Profile: ENVEOLI1501004EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
PVC free: Yes
© 2018 Alplan Kft.