Skip to main content

Schneider-Electric
GS2K3

TeSys GS - switch-disconnector-fuse - 3 P - 125A - NFC 22 x 58 mm
Net discounted price 196.50 EUR
Available when ordered (delivery time: 8 working day(s))
Barcode: 3389119410694
Tariff code: 8536508090

Link to the manufacturers site: GS2K3 - TeSys GS - switch-disconnector-fuse - 3 P - 125A - NFC 22 x 58 mm

Main

Range: TeSys

Product name: TeSys GS

Device short name: GS2K

Product or component type: Switch-disconnector-fuse

Poles description: 3P

Protected poles description: 3t

Contacts type and composition: 3 NO

[Ith] conventional free air thermal current: 125 A (at 40 °C)

[Ie] rated operational current: 100 A at 440 V 2 poles in series per phase DC-23A; 100 A at 440 V 2 poles in series per phase DC-23B; 100 A at 690 V AC-23A; 100 A at 690 V AC-23B; 125 A at 400 V AC-23A; 125 A at 400 V AC-23B; 125 A at 500 V AC-23A; 125 A at 500 V AC-23B

Fuse type: NFC

Fuse size: 22 x 58 mm

Network type: AC; DC

Network frequency: 50/60 Hz

Complementary

Type of operating handle: External right side; External frontal

mounting support: Plate

[Ui] rated insulation voltage: 750 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage: 8 kV

Rated operational power in W: 63 kW at 400 V; 90 kW at 500 V; 80 kW at 690 V

Making capacity: 1000 A at 400 V AC-23B

Breaking capacity: 10000 A at 400 V (AC-23B)

Short-circuit withstand: 20 kA

Mechanical durability: 10000 cycles

Electrical durability: 1000 cycles AC-23A; 1000 cycles DC-23A; 200 cycles AC-23B; 200 cycles DC-23B

Connections - terminals: Power circuit: bars20 mm²; Power circuit: lugs-ring terminals35…95 mm²

[Icm] rated short-circuit making capacity: 100 kA at 400 V with protection by gG fuses

Compatibility code: GS2K

Tightening torque: Power circuit: 12 N.m

Environment

Standards: IEC 60947-3

product certifications: CE

IP degree of protection: IP20 conforming to IEC 60529 (with terminal cover)

ambient air temperature for operation: -20…70 °C

Ambient air temperature for storage: -40…80 °C

Fire resistance: 850 °C fuse cover conforming to IEC 60695-2-1; 960 °C body conforming to IEC 60695-2-1

height: 162 mm

Width: 148 mm

Depth: 116 mm

Net weight: 1.5 kg

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 20.0 cm

Package 1 Width: 21.0 cm

Package 1 Length: 22.0 cm

Package 1 Weight: 1.835 kg

Unit Type of Package 2: S06

Number of Units in Package 2: 19

Package 2 Height: 75.0 cm

Package 2 Width: 60.0 cm

Package 2 Length: 80.0 cm

Package 2 Weight: 47.865 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP2003009EN

Circularity Profile: ENVEOLI2003009EN

© 2018 Alplan Kft.