Schneider-Electric
XMPC06C2374
Tariff code: 9032200090
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: XMPC06C2374 - PRESSURE SWITCH
Main
Range of produc: Telemecanique Pressure sensors XM
Pressure sensor type: Electromechanical pressure sensor
Pressure sensor name: XMP
Pressure rating: 6 bar
Fluid connection type: G 1/2 (female) conforming to ISO 228
Controlled fluid: Air (0…70 °C); Fresh water (0…70 °C); Sea water (0…70 °C)
Cable entry: 2 entries incorporating Pg 16 plastic cable gland, cable outer diameter: 12…15 mm conforming to NF C 68-300
Contacts type and composition: 3 NC snap action
Product specific application: -
Pressure switch type of operation: Regulation between 2 thresholds
Electrical connection: Screw-clamp terminals, clamping capacity: minimum : 2 x 4 mm²
Electrical circuit type: Power circuit
Scale type: Adjustable differential
Local display: Without
Sale per indivisible quantity: 1
Complementary
Adjustable range of switching point on falling pressure: 0.2…4.8 bar
Adjustment range high setting: 1…6 bar
Possible differential minimum at low setting: 0.8 bar
Possible differential minimum at high setting: 1.2 bar
Possible differential maximum at high setting: 4.2 bar
Destruction pressure: 30 bar
Type of decompression valve: Without
control type: ON/OFF knob
Terminal block type: 6 terminals
Pressure actuator: Diaphragm
Materials in contact with fluid: Canvas covered nitrile; Chromated zinc alloy
Enclosure material: PA impregnated with fibreglass
Operating position: Any position
Maximum operating rate: 10 cyc/mn
Repeat accuracy: 3.5 %
[Ui] rated insulation voltage: 500 V conforming to EN/IEC 60947-1
[Uimp] rated impulse withstand voltage: 6 kV conforming to EN/IEC 60947-1
Maximum resistance across terminals: 25 MOhm conforming to IEC 60255-7 category 3; 25 MOhm conforming to NF C 93-050 method A
Electrical durability: 1000000 cycles 1.5 kW, operating rate <10 cyc/mn, load factor: 0.4, 400 V AC 3 phases; 500000 cycles 3 kW, operating rate <10 cyc/mn, load factor: 0.4, 400 V AC 3 phases; 600000 cycles 1.5 kW, operating rate <10 cyc/mn, load factor: 0.4, 230 V AC 3 phases; 700000 cycles 2.2 kW, operating rate <10 cyc/mn, load factor: 0.4, 400 V AC 3 phases
Mechanical durability: 1000000 cycles
Setting: Knurled knob and nut
Net weight: 0.43 kg
Terminals description ISO n°1: (3-4)NC; (5-6)NC; (1-2)NC
Depth: 98 mm
height: 125 mm
Width: 57 mm
Environment
product certifications: EAC
Standards: EN/IEC 60947-4-1; CE
ambient air temperature for operation: -25…70 °C
Ambient air temperature for storage: -40…70 °C
Vibration resistance: 3 gn conforming to IEC 60068-2-6 (f = 10…500 Hz)
Shock resistance: 50 gn conforming to IEC 60068-2-27
Electrical shock protection class: Class I conforming to IEC 60536
IP degree of protection: IP65 conforming to EN/IEC 60529
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 6.5 cm
Package 1 Width: 11.5 cm
Package 1 Length: 17.0 cm
Package 1 Weight: 517.0 g
Unit Type of Package 2: S06
Number of Units in Package 2: 100
Package 2 Height: 73.5 cm
Package 2 Width: 60.0 cm
Package 2 Length: 80.0 cm
Package 2 Weight: 64.7 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP111130EN
Circularity Profile: N/A
© 2018 Alplan Kft.