Skip to main content

Schneider-Electric
VW3A4564

line choke - 0.038 mH - 613 A - 3 phases - 307 W - for variable speed drive
Barcode: 3389119201476
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: VW3A4564 - line choke - 0.038 mH - 613 A - 3 phases - 307 W - for variable speed drive

Main

range of product: Altivar

product or component type: Line choke

product compatibility: ATV61HC31N4D - line choke - 2 per drive; ATV61HC63N4D - line choke - 2 per drive; ATV61QC31N4 - line choke - 1 per drive; ATV71HC25N4 - line choke - 1 per drive; ATV71HC28N4 - line choke - 1 per drive; ATV71HC50N4 - line choke - 1 per drive; ATV71QC25N4 - line choke - 1 per drive

network number of phases: Three phase

range compatibility: Altivar 61; Altivar 71Q; Altivar 71; Altivar 61Q

device application: Reduction of current harmonics

value of inductance: 0.038 mH

[In] rated current: 613 A

saturation current: 1150 A

thermal losses: 307 W

electrical connection: Bare wires diameter: 13 mm

Complementary

supply frequency: 50...60 Hz

max current: 1.65 x nominal current (duration = 60 s)

maximum voltage drop at rated load: 5 %

electrical insulation class: Class F

minimum clearance distance: 5.5 mm IEC 60664

leakage distance: 11.5 mm conforming to IEC 60664

net weight: 73 kg

width: 385 mm

height: 440 mm

depth: 265 mm

Environment

standards: VDE 0160 level 1; EN 50178; IEC 60076 (with HD398)

IP degree of protection: Choke: IP00; Terminals: IP00

environmental characteristic: 3B1 conforming to IEC 721-3-3; 3C2 conforming to IEC 721-3-3; 3S1 conforming to IEC 721-3-3

pollution degree: 2 conforming to EN 50178

vibration resistance: 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6; 1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6

shock resistance: 15 gn for 11 ms conforming to IEC 60068-2-27

relative humidity: 0…95 %

ambient air temperature for operation: 45…55 °C (with current derating of 2 % per °C); 0…45 °C (without current derating)

ambient air temperature for storage: -25…70 °C

operating altitude: <= 1000 m without derating; 1000...3000 m with current derating 1 % per 100 m

Offer Sustainability

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)

Toxic heavy metal free: Yes

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation: X