Schneider-Electric
TM5SAI4PHK
Tariff code: 8538909999
Link to the manufacturers site: TM5SAI4PHK - Modicon TM5 I/O bővítő, komplett analóg bemenet, 4AI, PT100 / Pt1000, 16 bit
Main
Range of produc: Modicon TM5
Product or component type: Analog input module
analogue input number: 4
Analogue input type: Pt 100/Pt 1000 temperature probe - 200...850 °C
Analogue input resolution: 16 bits
Complementary
Device composition: Bus sub-base TM5ACBM11; Terminal block TM5ACTB12; I/O module TM5SAI4PH
Range compatibility: Modicon LMC058; Modicon M258
Product compatibility: Motion controller; Logic controller
Measurement resolution: 0.1 °C
Colour: White
Measurement error: < 0.037 % of full scale - 200...850 °C Pt 100/Pt 1000 at 25 °C
Temperature coefficient: 0.004 %FS/°C, analogue input type: temperature probe
Non-linearity: 0.001 %FS, analogue input type: temperature probe
Type of cable: Shielded cable
Isolation: No insulation between channels; 500 Vrms AC insulation between channel and bus
supply: Internal
[Us] rated supply voltage: 24 V DC -15...20 %
Common mode rejection: > 95 dB
Local signalling: 1 LED green for power supply; 1 LED red for power supply; 4 LEDs green for input status
Current consumption: 2 mA at 5 V DC bus; 46 mA at 24 V DC input/output
maximum power dissipation in W: 1.11 W
Marking: CE
Net weight: 0.065 kg
Environment
Standards: UL 508; CSA C22.2 No 142; IEC 61131-2; CSA C22.2 No 213
product certifications: GOST-R; cULus; C-Tick; CSA
Ambient air temperature for operation: 0…55 °C without derating (horizontal installation); 0…60 °C with derating factor (horizontal installation); 0…50 °C (vertical installation)
Ambient air temperature for storage: -25…70 °C
Relative humidity: 5…95 % without condensation
IP degree of protection: IP20 conforming to IEC 61131-2
Pollution degree: 2 conforming to IEC 60664
Operating altitude: 0...2000 m
Storage altitude: 0…3000 m
Vibration resistance: 1 gn at 8.4…150 Hz on DIN rail; 3.5 mm at 5…8.4 Hz on DIN rail
Shock resistance: 15 gn for 11 ms
Resistance to electrostatic discharge: 4 kV on contact conforming to EN/IEC 61000-4-2; 8 kV in air conforming to EN/IEC 61000-4-2
Resistance to electromagnetic fields: 1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3; 10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3
Resistance to fast transients: 1 kV (I/O) conforming to EN/IEC 61000-4-4; 1 kV (shielded cable) conforming to EN/IEC 61000-4-4; 2 kV (power lines) conforming to EN/IEC 61000-4-4
Surge withstand: 0.5 kV differential mode conforming to EN/IEC 61000-4-5; 1 kV common mode conforming to EN/IEC 61000-4-5
electromagnetic compatibility: EN/IEC 61000-4-6
Disturbance radiated/conducted: CISPR 11
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 7.500 cm
Package 1 Width: 9.000 cm
Package 1 Length: 11.000 cm
Package 1 Weight: 117.000 g
Unit Type of Package 2: S03
Number of Units in Package 2: 36
Package 2 Height: 30.000 cm
Package 2 Width: 30.000 cm
Package 2 Length: 40.000 cm
Package 2 Weight: 4.715 kg
© 2018 Alplan Kft.